6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1484 -
Operation accuracies
Protection functions
Accuracies
Distance protection
Distance measuring element
Static accuracy
Static angle accuracy
Operating time
5% at SIR
30,
10% at 30
SIR
50
5
of setting value
Typically 25ms + BO operating time (*1)
Overcurrent protection
Pick-ups
Operating time with definite timer
Operating time with inverse timer
5% of setting value (at I ≥ 0.5pu)
Typically 35ms + BO operating time (*1)
IEC curve
:
5% of theoretical value
for 2
Multiple of threshold value
10 and
TMS=1
IEEE curve:
10% of theoretical value
for 2
multiple of threshold value
10 and
TMS=1
Earth Fault Protection
Pick-ups
Operating time with definite timer
Operating time with inverse timer
3% of setting value
Typically 35ms + BO operating time (*1)
IEC curve
:
5% of theoretical value
for 2
Multiple of threshold value
10 and
TMS=1
IEEE curve:
10% of theoretical value
for 2
multiple of threshold value
10 and
TMS=1
Over / under voltage protection
Pick-ups
Operating time
5% of setting value
Typically 35ms
Breaker Failure (BF) Protection
Operating time of overcurrent element
Resetting time of overcurrent element
Typically 20ms
Maximum
15ms
Thermal overload protection
Pick-ups
Operating time
5% of setting value
10% of setting value
Negative overcurrent protection
Pick-ups
Operating time
5% of setting value (at I ≥ 0.5pu)
Typically 35ms
Broken conductor protection
Pick-ups
Operating time
5% of setting value (at I ≥ 0.5pu)
Typically 35ms
Autoreclose
Operating time of synchronism check
element
Operating time of UV and OV elements
Typically 35ms
Typically 35ms
Fail safe relay operating time
Typically 20ms
(*1)Typically 3—6ms
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......