6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 505 -
when the interlock check is required in the select logic, use the connection point (PLC#1;e.g.,
DEV01_CL_INTERLOCK). Alternatively, if the interlock check is not required, use the
connection point (PLC#2); e.g., DEV01_CL_COMMAND”. PLC#1 and PLC#2 are shown in
Table 4.1-2.
SPOS01 function (Function ID:
510001)
510001 8601011DC6
DEV01_CL_COMMAND
Operate command
without ILK
† condition
ILK
† condition (“ON”) passed
PLC in DIR operate
DIR
DIR
510001 800101EE32
510001 7001016D08
SPOS01-On
Signals from user-PLC logic
Output
Selection logic in SPOS01
0.1s
0
t
0.6s
0
t
&
&
&
Select condition
‡
1
≥
ON-control command requiring ILK checking
†
(PLC#1 connection point)
DEV01_CL_INTERLOCK
510001 800101EE33
ON-control command requiring no ILK checking
†
(PLC#2 connection point)
Operate command
with ILK
†
condition
For DIR operation
For DIR operation
“SPOS01_OSL_BO_CSF”
(510001
_
8601011DC6)
Selection
“Failed”
To BO connection
Selection
“success”
To
“Wait for a command”
To
“Wait for a next
command
”
Figure 4.1-10 Select ‘On’ using the PLC function in SPOS01
††
†Note: The software interlocking (ILK) function can provide the operation criteria for
“On”. The ILK function is discussed separately; note that the operation criteria is
defined in the ILK function itself (i.e., the user cannot set the condition).
††
Note: To identify the input and output signals of the other SPOS logics, see Table 4.1-2
and Table 4.1-9.
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
Output signal to BO
The SPOS01 function, in Figure 4.1-10, can issue a “Select success” signal at the output-point
“SPOS01_OSL_BO_CSF”
1
.
1
Note: The signal “SPOS01_OSL_BO_CSF” is the same as that shown in Figure 4.1-2.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......