6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 511 -
Table 4.1-7 PLC connection points (Input signal for select condition logic)
Signal Number
Signal Name
Description
M/O
510001 800101EE61
SPOS01IN_TMP_31
SPOS01 additional failure condition (PLC#1)
O
510001 800102EE61
SPOS02IN_TMP_31
SPOS02 additional failure condition (PLC#1)
O
510001 800103EE61
SPOS03IN_TMP_31
SPOS03 additional failure condition (PLC#1)
O
….
….
….
510001 800114EE61
SPOS20IN_TMP_31
SPOS20 additional failure condition (PLC#1)
O
510001 810101EE62
SPOS01IN_TMP_32
SPOS01 user configurable select condition (PLC#2)
O
510001 810102EE62
SPOS02IN_TMP_32
SPOS02 user configurable select condition (PLC#2)
O
510001 810103EE62
SPOS03IN_TMP_32
SPOS03 user configurable select condition (PLC#2)
O
….
….
….
510001 810114EE62
SPOS20IN_TMP_32
SPOS20 user configurable select condition (PLC#2)
O
510001 820101ED50
SPOS01IN_TMP_28
SPOS01 control hierarchy condition (PLC#3)
M
510001 820102ED50
SPOS02IN_TMP_28
SPOS02 control hierarchy condition (PLC#3)
M
510001 820103ED50
SPOS03IN_TMP_28
SPOS03 control hierarchy condition (PLC#3)
M
….
….
….
510001 820114ED50
SPOS20IN_TMP_28
SPOS20 control hierarchy condition (PLC#3)
M
Table 4.1-8 PLC monitoring points (Output signal for select condition logic)
Signal Number
Signal Name
Description
510001 8001011F54
SPOS01_SC_ST_ERR
SPOS01 select command mode is invalid.
510001 8001021F54
SPOS02_SC_ST_ERR
SPOS02 select command mode is invalid.
510001 8001031F54
SPOS03_SC_ST_ERR
SPOS03 select command mode is invalid.
….
….
….
510001 8001141F54
SPOS20_SC_ST_ERR
SPOS20 select command mode is invalid.
510001 8101011F59
SPOS01_F_QLT_SPP
Event suppression detected (SPOS01)
510001 8101021F59
SPOS02_F_QLT_SPP
Event suppression detected (SPOS02)
510001 8101031F59
SPOS03_F_QLT_SPP
Event suppression detected (SPOS03)
….
….
….
510001 81010A1F59
SPOS20_F_QLT_SPP
Event suppression detected (SPOS20)
510001 8201011F5A
SPOS01_F_BI_ERR
BI connection error detected(SPOS01)
510001 8201021F5A
SPOS02_F_BI_ERR
BI connection error detected(SPOS02)
510001 8201031F5A
SPOS03_F_BI_ERR
BI connection error detected(SPOS03)
….
….
….
510001 8201141F5A
SPOS20_F_BI_ERR
BI connection error detected(SPOS20)
Table 4.1-9 PLC monitoring points (On/Off Output-signal)
Signal Number
Signal Name
Description
510001 8601011DC6
SPOS01_OSL_BO_CSF
SPOS01 select (ON) command for Binary Output.
510001 8601021DC6
SPOS02_OSL_BO_CSF
SPOS02 select (ON) command for Binary Output.
510001 8601031DC6
SPOS03_OSL_BO_CSF
SPOS03 select (ON) command for Binary Output.
….
….
….
510001 8601141DC6
SPOS20_OSL_BO_CSF
SPOS20 select (ON) command for Binary Output.
510001 8A01011DC4
SPOS01_FSL_BO_CSF
SPOS01 select (OFF) command for Binary Output.
510001 8A01021DC4
SPOS02_FSL_BO_CSF
SPOS02 select (OFF) command for Binary Output.
510001 8A01031DC4
SPOS03_FSL_BO_CSF
SPOS03 select (OFF) command for Binary Output.
….
….
….
510001 8A01141DC4
SPOS020_FSL_BO_CSF
SPOS20 select (OFF) command for Binary Output.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......