6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1513 -
DPOS01 setting (exercise)
We need to set [
DPOS01-EN
]=
On
for DPOS01 in order that we can control the CB by MIMIC
at local-end. Table 4 and Figure 6 show the setting items in the DPOS01 controlling.
DPOS inputs
When [
DPOS01-CTRN
]=
On
is set for general CB controls (#1), we can make settings NOPSG
(N/O) and NCLSG (N/C) to get CB aux. contact signals in DPOS01.
[
DPOS01A-NOPSG
]=
BI1
and [
DPOS01A-NCLSG
]=
BI2
(#2, #3)
[
DPOS01B-NOPSG
]=
BI1
and [
DPOS01B-NCLSG
]=
BI2
(#4, #5)
[
DPOS01C-NOPSG
]=
BI1
and [
DPOS01C-NCLSG
]=
BI2
(#6, #7)
DPOS outputs
When [
DPOS01-PLSM
]=
Var
is set, OPEN or CLOSE command will be issued if Closing or
Opening keys are pushed (#8).
We need have setting [
DPOS01-FEXBORD
]=
BO3 RE
(#9) in order that the command has been
issued without discrepancy (see Figure 5). Similarly, we have the setting [
DPOS01-
OEXBORD
]=
BO4 RE
(#10).
Table 4 Exercise in DPOS01 (Function ID: 512001)
Step
Signals/ [Settings]
Signal/[Setting] contents
0
[
DPOS01-EN
]
DPOS01 ready switch
1
[
DPOS01-CTRN
]
DPOS01 switch
2
[
DPOS01A-NOPSG
]
N/O setting at phase-A
BI1
BI1 circuit output
3
[
DPOS01A-NCLSG
]
N/C setting at phase-A
BI2
BI2 circuit output
4
[
DPOS01B-NOPSG
]
N/O setting at phase-B
BI1
BI1 circuit output
5
[
DPOS01B-NCLSG
]
N/C signal at phase-B
BI2
BI2 circuit output
6
[
DPOS01C-NOPSG
]
N/O setting at phase-C
BI1
BI1 circuit output
7
[
DPOS01C-NCLSG
]
N/C setting at phase-C
BI2
BI2 circuit output
8
[
DPOS01-PLSM
]
OPEN/CLOSE pulse adjustment
9
[
DPOS01-FEXBORD
]
OPEN validity setting
BO4 RE
Read-back signal on BO4 circuit
10
[
DPOS01-OEXBORD
]
CLOSE validity setting
BO3 RE
Read-back signal on BO3 circuit
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......