6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 443 -
incrementing from either 0 or 1. The return number can be set with
[
CNTRV
].
3. Select-cancel timer: If the selection of a target device is made, but the control operation
of the selected device is not carried out in a predetermined time
limit, the selection is canceled. The time limit can be set using
[
TSC
]; the range is between 30 and 300sec. having a 1sec. step.
4. Time out:
When the selection of the target device and its control execution is
made, the selection will be canceled automatically after the setting
time [
EXEWAIT
] if the control result is not received at the IED from
the target device. The setting time ranges from 30 to 300sec. in 1
sec. steps.
5. Counter limit:
The maximum value of the counters can be set between 9 and
2,147,483,647 using [
CNTVALMAX
]. The default setting is 999,999.
6. Quality signal:
If “q” or “Quality” information shall not be taken for controlling, set
On
for setting [
QBLK
]. The
QBLK
clears the content of quality
information, so that control operation can be achieved with the
absence of quality information.
3.4.5
Setting
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......