6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 305 -
2.20.9
Setting
FS (Function ID: 48B001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
FS-EN
Off / On
- Fail safe scheme switch
Off
OCFS-EN
Off / On
- OCFS scheme switch
Off
OCDFS-EN
Off / On
- OCDFS scheme switch
Off
EFFS-EN
Off / On
- EFFS scheme switch
Off
OCMFS-EN
Off / On-T / On-S
- OCMFS scheme switch
Off
UVFS-EN
Off / On
- UVFS scheme switch
Off
UVSFS-EN
Off / On
- UVSFS scheme switch
Off
DUVFS-EN
Off / On
- DUVFS scheme switch
Off
OC
OCFS
0.10 -
50.00
0.50 -
250.00
A OCFS relay operating value
1.00
5.00
OCD
OCDFS
0.05 -
0.20
0.25 -
1.00
A OCDFS relay operating value
0.10
0.50
TOCDFS
0.00 - 300.00
s Extended time of OCDFS operating
10.10
EF
EFFS
0.10 -
50.00
0.50 -
250.00
A EFFS relay operating value
0.20
1.00
UV
UVFS
5.0 - 130.0
V UVFS relay operating value
46.0
UVS
UVSFS
5.0 - 130.0
V UVSFS relay operating value
80.0
DUV
DUVFS
1 - 20
V DUVFS relay operating value
5
TDUVFS
0.00 - 300.00
s Extended time of DUVFS operating
10.10
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......