2-2. Type using ring terminals and 24-60 Vdc
IED case structure
Type using compression terminals
✓
Type using ring terminals
DC rated voltage
110-250 Vdc
✓
24-60 Vdc
Figure-11.D
illustrates external connection around the power supply module (PWS). During dielectric
voltage testing, short-wires and a short-bar attached on the PSW shall be carefully handled; follow
the below instructions (1), (2) and (3).
(1) The short-wire between terminal screw No.35 and No.36
Remove the short-wire for undertaking the dielectric voltage test. If the short-wire is not
removed, the IED will be damaged.
After the test, reconnect the short-wire to the original positons.
(2) The Short-bar between terminal screw No.37 and FG
Never remove the short-bar. If the short-bar is removed, the IED will be damaged.
(3) The short-wire between terminal screw No.38 and FG
Never remove the short-wire. If the short-wire is removed, the IED will be damaged.
[IO#*]
T*
T*
[IO#*]
T*
[VCT#*]
TC*
(1)
PWS
29
30
31
32
38
DC/DC
(+)
(-)
36
3
1
2
4
FAIL1
9
7
8
10
FAIL2
FG
35
37
y
BIO
BIO
(3)
(2)
Figure-11.D Short-wires and a short-bar, around the PWS, for Type using ring terminals and 24-60Vdc
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......