6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 721 -
(ii)
Receiving “Select command Off” from the remote-end
Figure 4.8-3 outlines the reception of the Select command ‘Off’ from the remote-end.
Signal reception
IEC61850
Select command Off from the remote-end
Signal output
Select
decision
Success
Failed
Select logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command On from the remote-end
Select command On from the local-end
Select command Off from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Figure 4.8-3 Outline of Select command ‘Off’
Input point mapped from the communication
Figure 4.8-4 shows the Select logic when a “Select command Off (Remote-OFF-Control)” signal
is applied at the input-point “DEV01_CONTROL_REQ”.
Output signal to BO
The DPOS01 function, in Figure 4.8-4, can issue a “Select success” signal at the output point
“DPOS01_FSL_BO_FLG” when the DPOS01 function determines that the received “Select
command Off (Remote-OFF-Control)” signal is true. If the DPOS01 function determines that
the “Remote-OFF-Control” signal is not true, the DPOS01 function returns to the “Wait for a
command” stage.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......