Setting self-impedances
With regard to the self-impedances, the user should set the resistance of the self-
impedances for settings [
FL_Raa
], [
FL_Rbb
] and [
FL_Rcc
] and set the reactance of the
self-impedances for settings [
FL_Xaa
], [
FL_Xbb
] and [
FL_Xcc
].
Setting mutual-impedances
With regard to setting the mutual-impedances, the user should set the resistance of the
mutual-impedance for settings [
FL_Rab
], [
FL_Rbc
] and [
FL_Rca
] and set the reactance
of the mutual-impedances for settings [
FL_Xab
], [
FL_Xbc
], and [
FL_Xca
].
Setting compensation factors
If imbalanced impedances are considered, Equations (2.23-10) and (2.23-11) are used
to acquire the zero-sequence and positive-sequence impedances. The calculations are
executed internally by the FL function; thus, the user does not need to consider them
in the matrix setting mode.
(iii)
Assumption of fault direction
The user can select the direction for the FL computation to be in either the forward or the
reverse direction. When the forward direction is selected, other protection elements related to
the FL computation should have the same direction If the user selects the reverse direction,
other corresponding functions should have the reverse direction. Otherwise, the FL
computation will fail to start.
Figure 2.23-3 illustrates the relationship between the location of faults relative to the
direction of FL computations. The user should set the scheme switch [
FL_Dir
]
Forward
if the
fault location computation is required for faults that occur in the forward direction. Conversely,
set [
FL_Dir
]
Reverse
if the fault location computation is required for faults that occur in the
reverse direction.
Figure 2.23-3 Forward fault and reverse fault
Bus G
IEF
Fault
a. Fault in Forward direction
If
b. Fault in Reverse direction
IED
Fault
Bus G
If
IEF
IED
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......