6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 667 -
Table 4.5-4 Mapping signals for ISCSO1 object.
Object_reference
Attribute
Type
FC Signal Number
Signal Name
Ctrl/GGIO1301$ISCSO1$origin
orCat
orCategory
ST
5410013015011D23
TTIM01_TIM_ORCAT
Ctrl/GGIO1301$ISCSO1$origin
orIdent
Octet64
ST
5410016A15011FA7 TTIM01_TIM_ORIDENT
Ctrl/GGIO1301$ISCSO1
stVal
INT32
ST
5410013215011D20
TTIM01_TIM_SEC_VAL
Ctrl/GGIO1301$ISCSO1
q
Quality
ST
5410013115011D21
TTIM01_TIM_QLT
Ctrl/GGIO1301$ISCSO1
t
Timestamp
ST
5410019015011D22
TTIM01_TIM_TIM
Ctrl/GGIO1301$ISCSO1
stSeld
BOOLEAN
ST
5410010015011D91
TTIM01_TMP_01
Ctrl/GGIO1301$AnIn1$mag
f
FLOAT32
MX
5410013215011D20
TTIM01_TIM_SEC_VAL
Ctrl/GGIO1301$AnIn1
q
Quality
MX
5410013115011D21
TTIM01_TIM_QLT
Ctrl/GGIO1301$AnIn1
t
Timestamp
MX
5410019015011D22
TTIM01_TIM_TIM
Note: “Status (ST)” and “Measurement (MX)” are defined in the function constraint (FC)
of the IEC 61850 standard.
Drag and drop
Figure 4.5-6 orCat attribute mapped into ISCSO1 object of GGIO1301
(iii)
Mapping input data
The TTIM01 function can receive three commands “select, operate, and cancel. Thus, the user
will need to map the input-point “TOTAL01_CMM_REQ”. Table 4.5-5 shows the input-point
“
TOTAL01_CMM_REQ” and the Object reference “Ctrl/GGIO1301$ISCSO1$”; the user should
map the input-point to the Object reference having
attributes CO and CF in FC†. Figure 4.5-7
shows how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......