6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 427 -
2.28.2
Setting
CLP(Function ID:
481001) at Common
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
CLP-EN
Off / On
- Cold load protection scheme switch
Off
CLP
CLP-SG
Group1 / Group2 /
Group3 / Group4 /
Group5 / Group6 /
Group7 / Group8
- Applied setting group at cold load mode
Group1
TCLP-EN
0 - 10000
s Cold load enable time
100
TCLP-RESET
0 - 10000
s Cold load reset time
100
DOEN CLP-DOEN
Off / On
- Cold load drop-out enable
Off
OCCLP
0.02 -
3.00
0.10 -
15.00
A Cold load drop-out current threshold
0.50
2.50
TCLP-DO
0.00 - 100.00
s Cold load drop-out time
0.00
Test tool(Function ID: 481001)
Item
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Function test
CLP-Test
Off / STATE0 /
STATE3
- Forcibly changing to CLP state
Off
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......