6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 569 -
DPSY01 function (Function ID: 511001)
S
R
0.1
– 50.0 s
[
DPSY01-CPW
]
PLC
DEV01_CONTROL_REQ
Command
“Remote-Closing-Control”
511001
_
7002016D08
ILK condition (“Closing”) passed
DPSY01-Close
&
&
1
≥
1
≥
1
≥
&
&
Input
Output
Operate logic in DPSY01
“DPSY01_OEC_OK_CS”
(511001 8102011E82)
Operate Command
with ILK
†
condition
Operate Command
without
condition
&
Operate Command
with ILK
†
condition & synchro-checking
Operate Command
with
synchro-checking
&
Assign to BOs
Operate condition
‡
[
DPSY01-LGCTRCON
]
Fixedlogic
Fixedlogic
[
DPSY01-LGCFEXOT
]
DPSY01IN_TMP_35
511001 810201EE57
User configurable condition
(PLC#1 connection point)
&
&
“DPSY01_OEX_BO”
§§
(511001 8202011DD3)
To BO connection
[
DPSY01-PLSM
]
*
Var
Fix
Operate Failed
[
DPSY01-RST
]
ASEQ
§
function
” is in progress
ASEQ_MULTI_SEL
“DPSY01_OEC_OK_CSF”
(511001 8002011E7F)
“DPSY01_EX_FFL”
‡‡
(511001 8602011E91)
To
“Wait for a command”
&
&
DPSY01IN_TMP_44
511001 820201EE5E
User configurable condition
(PLC#2 connection point)
1
≥
&
“DPSY01_EX_CMP”
(511001 8002011E93)
Operate Completed
1.0s- 100.0s
0
t
From SYNCHK
SYNC01-SYN_CLC
(560001 850B011F59)
“DPSY01_OEC_OK_CSF”
(511001 8002011E7F)
S
R
Detection of state-change in
a device
“DPSY01_EX_CMP”
(511001 8002011E93)
Figure 4.2-20 Operate ‘Closing’ from the remote-end in DPSY01
††
†Note: The ILK function can provide the operation criteria for “Closing”.
‡Note: An “operate condition” signal is generated in the operate-condition logic (see
Fixlogic
is set for scheme switch [
DPSY01-LGCTRCON
]. If an
alternative “operate-condition” is required, it can be programmed by the user and
used to replace the signal generated by the original operated-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #1 “User-configurable condition”. That is, set the scheme switch
[
DPSY01-LGCTRCON
] to
PLC
and use “DPSY01IN_TMP_35”.
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when
Fixlogic
is set for scheme switch
[
DPSY01-LGCFEXOT
]. The “Operate completed” signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.2-20. The
user-programmed logic is connected internally to the signal “Operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point #2 “User-configurable condition”. That is, set the scheme switch [
DPSY01-
LGCFEXOT
] to
PLC
and use “DPSY01IN_TMP_44”.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......