6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1061 -
Setting
Metering settings in MES (Function ID: 710001)
Setting item
Range
Unit
s
Contents
Default
setting value
Notes
Display Value
Primary/Secondary
–
Display selection of primary or secondary
Primary
Power
Send/Receive
–
Power flow definition (Supply or absorb)
Send
Current
Lead/Lag
–
The angle compared with the voltage
Lead
PF Sign
AP/AP+RP
–
Denison of the sign of the power factor
AP+RP
I-Valid Level
0.10 to 5.00
%
Cutting off small entering current
4.00
V-Valid Level
0.10 to 5.00
%
Cutting off small applied voltage
0.30
I-Display Unit
A/kA
–
Current shown in Ampere or Kilo-Ampere
kA
V-Display Unit
V/kV
–
Voltage shown in Volt or Kilo-Volt
kV
P-Display Unit
kW/MW
–
Active power shown in Kilo- or Mega-watt
MW
Q-Display Unit
kvar/Mvar
–
Reactive power shown in Kilo- or Mega-var
Mvar
S-Display Unit
kVA/MVA
–
Apparent power shown in Kilo- or Mega-
VA
MVA
Statistics settings in MES (Function ID: 710001)
Setting item
Range
Unit
s
Contents
Default
setting value
Notes
Wh-Display Unit
kWh/MWh
–
Watt-hour shown in Kilo- or Mega-Wh
MWh
varh-Display Unit
kvarh/Mvarh
–
Var-hour shown in Kilo- or Mega-varh
Mvarh
Demand settings in MES (Function ID: 712001)
Setting item
Range
Unit
s
Contents
Default
setting value
Notes
Demand_period
1min / 5min /
10min / 15min /
30min / 60min
–
Period of demand calculation
10min
Dead-band setting in MES (Function ID: 710001)
Setting item
Range
Unit
s
Contents
Default
setting value
Notes
ISD
0.00 to 50.00
%
Sending Dead Band in current
5.00
VSD
0.00 to 50.00
%
Sending Dead Band in voltage
0.60
P/Q/SSD
0.00 to 50.00
%
P/Q/S Sending Dead Band
5.00
PFSD
0.00 to 1.00
–
PF Sending Dead Band
0.02
FSD
0.00 to 50.00
%
F Sending Dead Band
0.50
Wh/varhSD
0.0 to 999.9
–
Wh/varh Sending Dead Band
1.0
PhaseSD
0.0 to 90.0
deg
Phase Sending Dead Band
0.5
PeriodSD
0 to 4
–
Period of Sending Dead band
0
dVSD
0.00 to 50.00
%
dV Sending Dead Band
0.60
Setting of Test in MES (Function ID: 710001)
Setting item
Range
Unit
s
Contents
Default
setting value
Notes
Commercial Test
OFF / ON
–
Commercial Test Switch
OFF / ON
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......