6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 508 -
2.
Set the scheme switch [
SPOS01-LGSLFFCT
] to
Fixed logic
.
How to replace the original logic
If the user wishes to replace the select condition logic completely, the user can replace it using
the PLC connection point “User configurable condition”.
1.
Connect the user-customized logic using SPOS01IN_TMP_32, which is listed as
PLC#2 in Table 4.1-7.
2.
Set the scheme switch [
SPOS01-LGSLFFCT
] to
PLC
.
Select condition
SPOS01 function (Function ID: 510001)
User configurable condition (PLC #2connection point)
Same Directional
Controlling Event
OFF
[SCDEN]*8
Fixedlogic
[
SPOS01-LGSLFFCT
]
To selection logic
From Control hierarchy (e.g. 43RL) (PLC#3 connection point)*9
[
SPOS01-CTREN
]
On
Users must setup this condition correctly
Function
“Automatic sequence control” is in progress
Additional condition (PLC#1 connection point)
CBK_STATE
Command blocking
*
1
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
Tripping
*
4
(“General trip”)
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
GEN. TRIP
Unmatched condition detected *5
Event suppression detected *6
BI board connection error detected*7
SPOS01IN_TMP_31
510001 800101EE61
SPOS01IN_TMP_32
510001 810101EE62
SPOS01IN_TMP_28
510001 820101ED50
SERI_ERR
Command
“ON control” received
Command
“OFF control” received
received
SPOS01_STATE
&
&
&
&
&
&
1
≥
1
≥
Unmatched condition detected *5
Event suppression detected *6
= SPOS01_F_QLT_SPP
BI board connection error detected*7
= SPOS01_F_BI_ERR
(510001 810101F59)
(510001 820101F5A)
(510001 0001011001)
From CMNCTRL serious error detection
Figure 4.1-13 Select condition logic for ON/OFF in SPOS01
*10
1
Note: “Command blocking” disables any operation except its own; the “Command
blocking” is initiated by the status of “CBK” in a software switch controller
(SOFTSW).The IEC 61850 standard defines command blocking as “CmdBlk”. For
more information on “CBK”, see Chapter
Control and monitoring application:
Software switch controller. See the signal “S4301_STAEE of Table 4.1-6.
2
Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS.
3
Note: If the event “device-travelling is detected, it indicates that another operator is
changing the statuses of a device. Thus, the IED should inhibit the operation of
any device for the duration that the event is detected. The detecting signal is
donated as “Travelling OR” in Table 4.1-6.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......