6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1368 -
(MICS Ed.1)
RPSB class
Attribute Name Attr. Type Explanation
T M/O GRZ200
LNName
Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class
M
OpCntRs
INC
Resetable operation counter
O
N
Status Information
Str
ACD
Start (Power Swing Detected)
C1
Y
Op
ACT
Operate (Out of step Tripping)
T
C2
N
BlkZn
SPS
Blocking of correlated PDIS zone
C1
Y
Setting
ZeroEna
SPG
Zero Enable
O
N
NgEna
SPG
Negative Sequence Current Supervision Enabled
O
N
MaxEna
SPG
Max Current Supervision Enabled
O
N
SwgVal
ASG
Power Swing Delta
O
Y
SwgRis
ASG
Power Swing Delta R
O
N
SwgReact
ASG
Power Swing Delta X
O
N
SwgTmms
ING
Power Swing Time
O
Y
UnBlkTmms
ING
Unblocking Time
O
N
MaxNumSlp
ING
Maximum number of pole slips until tripping (Op, Out of step
tripping)
O
N
EvTmms
ING
Evaluation time (time window, Out of step tripping)
O
N
Condition C1: Mandatory if RPSB is used for “Power swing blocking”
Condition C2: Mandatory if RPSB is used for “Out of step tripping”
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......