6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 459 -
†Note: Although the “LED_RST_COM” signal is connected previously with several LEDs,
by the manufacturer, user can also connect the signal with the LEDs. See section
3.6.4 for how to connect.
(iii)
Operate condition
Figure 3.6-8 shows the operate condition logic of the LEDR function, which is used to determine
a reset-condition for the operation.
Operate condition
LEDR function (Function ID: 528001)
To operate logic
Control hierarchy (e.g. 43RL) (PLC connection point) *5
IED serious error detected
[
LEDDR1_EN
]
On
Users must setup this condition correctly
Function
“Automatic sequence control” is in progress
S4301_STATE
Command blocking
*
1 (S4301 defines
”Blocked”)
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
LEDR01_CTRL_RIGHT
528001 820701ED50
SERI_ERR
&
&
1
≥
Unmatched condition detected *4
Figure 3.6-8 Operate condition logic in LEDR
*6
*1
Note:
“Command blocking” disables all operation except for its own: the “command
blocking” function is initiated by the status of “S4301” in a software controller
(SOFTSW). The IEC 61850 standard defines the “command blocking” function as
“CmdBlk”. For more information on S4301, see Chapter
Control and monitoring
application: Software switch control function. See the signal “S4301_STATE” of
Table 3.6-2.
*2
Note:
“Double Command Blocking (DCB)” is an operation philosophy in the
common control function (CMNCTRL). It can be used to protect the substation.
The user can program it using GR-TIEMS. The DCB operating signal is denoted
as “DCB RCV_OR in Table 3.6-2. For more information, see Chapter
Control and
monitoring application: Common controls.
*3
Note:
If the event “device-travelling” is detected in the CMNCTRL function, it
indicates that another operator is changing the status of a device. Thus, the IED
should inhibit the operation of any device for the duration that the event is
detected. The detecting signal is denoted as “Traveling OR” in Table 3.6-2.
*4
Note:
Criteria “unmatched conditions” are decided when the “Test-bit status” in a
command is not identical to the “IED test status”.
*5
Note:
The user must program the PLC logic for “Control hierarchy condition”. The
user must connect that to the select condition logic using the connection point
“LEDR01_CTRL_RIGHT”. For more information, see chapter
Control and
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......