6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
93
ZS (Function ID
:
430001
)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Z1XS-
MhoR.EN
Off / On
- Z1XS resistive reach use or not (for Mho)
Off
Z1XS-R.Angle
30 - 90
deg Z1XS resistive reach characteristic angle
75
Z1XS-R.Reach
0.10 -
500.00
0.01 -
100.00
- Z1XS resistive reach
25.50
5.10
Z1XS-
MhoDX.EN
Off / On
-
Z1XS directional-X characteristic use or not
(for Mho)
Off
Z1XS-DX.Angle
0 - 60
deg Z1XS directional-X characteristic angle
30
Quad
Z1XS-X.Reach
0.10 -
500.00
0.01 -
100.00
- Z1XS reactance reach
12.00
2.40
Z1XS-
X.GrAngleEN
Off / On-Set / On-
Adapt
- ZS gradient characteristic
Off
Z1XS-R.Angle
30 - 90
deg Z1XS resistive reach characteristic angle
75
Z1XS-R.Reach
0.10 -
500.00
0.01 -
100.00
- Z1XS resistive reach
25.50
5.10
Z1XS-DX.Angle
0 - 60
deg Z1XS directional-X characteristic angle
30
Z1XS-DR.Angle
0 - 60
deg
Z1XS directional-R characteristic angle (for
Quad)
5
TZ1XS
0.00 - 100.00
s Z1XS operation delay time
0.00
Z1XS-CovCoeff
1.5 - 10.0
- Covered characteristic size coefficient
1.5
Output
Z1XS-MSDET
Off / On
-
Multi-phase or non-earth-fault condition is
used or not
On
Z1XS-PSBBlk
Non / Block
- Z1XS operation block or not by PSB detection
Block
Z1XS-LEBlk
Non / Block
- Z1XS blocked or not by Load encroachment
Non
Z1XS-ARCBlk
Non / Block
- Autoreclose execution block by Z1XS-trip
Non
Z1XS-OCFS-
EN
Off / On
- Fail-safe OC for Z1XS-trip
Off
OCF1XS
0.02 - 5.00
0.10 -
25.00
A Fail-safe OC operation level for Z1XS-trip
0.20
1.00
Z1XS-SOTF
Off / On
- SOTF using Z1XS
Off
Note 1:
On-Adapt
is only applicable when
Forward
is set for ZS.
Note 2: When
On-Adapt
is set for the scheme switch [
Z*S-X.GrAngleEN
], the setting
value [
ZSF-X.GrAngle1
] will be calculated by itself. However, the user should
enter a value for [
ZSF-X.GrAngle2
] regardless of the setting of the [
ZS-
X.GrAngleEN
].
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......