6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1071 -
(iii)
Error outputs with contacts and binary output circuits
Automatic supervision function drives a contact of the power supply module (PWS)† when an
error occurs without warning; additionally, binary output circuits (BOs‡) will be locked out to
drive when serious error (Level 1=Critical error) is detected.
Table 10.1-4 FAIL contact, BO, LED outputs depending on levels
Error
Levels
PWS† contact outputs
BO‡ locked out
Error
LED
FAIL1 terminal
FAIL2 terminal
Screw No. 1
(N/C)
Screw No. 3
(N/O)
Screw No. 7
(N/C)
Screw No. 9
(N/O)
0: No error
Open
Closed
Open
Closed
Not locked out
Off
1:Serious
Closed
Open
Closed
Open
Locked out
On
2:Serious(Comm.)
Open
Closed
Open
Closed
Not locked out
On
3:Minor
Open
Closed
Open
Closed
Not locked out
On
4:Alarm
Open
Closed
Open
Closed
Not locked out
Off
5:Warning
Open
Closed
Open
Closed
Not locked out
Off
Error output by PWS contact
†
If serious error (Level1) is detected by Automatic supervision function, normally-closed-contact
(N/C) on FAIL1 and FAIL2 terminals is closed. On the other hand, the N/O contact is open on
the serious error, as shown in Table 10.1-4.
Locking out of BO circuit operation
‡
BO is locked out to operate, when serious error (Level1) occurs. Serious error stops trip signal
generations to the BO circuit. When serious error is removed, the operation will be recovered.
†Note: See Chapter
Technical description: Power supply module. FAIL1 (FAIL2) contact
is in Form-C; terminal-screw No. 2 & 4 (8 &10) are provided with the common.
‡Note: BO is discussed in Chapter
Technical description: Binary output circuit.
(iv)
Affection of application operation by error levels
The error levels influence the operation of relay and control and monitoring application.
Table 10.1-5 Operation states in the IED applications affected by the error levels
Levels
Relay applications
Control and monitoring applications Notes
0: No error
–
–
1: Serious
Stopped
Stopped
2: Serious (Comm.)
Not affected†
Not affected
3: Minor
Not affected
Stopped
4: Alarm
Not affected
Not affected
5: Warning
Not affected
Not affected
†Note: Serious (Comm.) can be related to communication of tele-protection applications.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......