6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 297 -
2.19.1
Operation and characteristic
The ICD function examines the ratio of a second harmonic current (I2f) to the fundamental
current (I1f) in each phase. If the ratio
|I
2f
| |I
1f
|
⁄
is larger than the setting [
ICD-2f
], the ICD
function is able to identify the presence of inrush currents. Figure 2.19-1 illustrates the
characteristic; the operation region is designated by the hatched area; the operation threshold
is set with the [
ICD-OC
].
I1f
0
I2f
ICD–OC
θ
ICD-2f (%) = tanθ×100
|I2f|/|I1f|
ICD-2f(%)
|I1f|
ICD–OC
&
ICD
Figure 2.19-1 ICD characteristic and operation region
As shown in Figure 2.19-1, the user should set both the [
ICD-2f
] and [
ICD-OC
] when the
second harmonic inrush current should be detected. The user should set
On
for the scheme
switch [
ICD-EN
] to enable the ICD operation.
2.19.2
Scheme logic
Figure 2.19-2 illustrates the ICD logic. When second harmonic inrush current is detected, the
ICD signal will be received by other protection functional elements.
8300001C23
8200001C22
8000001C20
8100001C21
ICD
A
B
C
ICD-B
ICD-C
ICD-A
≥1
ICD-OR
To OC, SOTF-OC, STUB-OC
To EF, OCN, BCD
Figure 2.19-2 ICD logic
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......