6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1489 -
Functional Data (5/5)
Phase to Phase Undervoltage Protection
1
st
, 2
nd
undervoltage threshold
5.0 to 130.0V in 0.1V steps
Delay type
DTL, IDMT, Original
Drop-out/pick-up ratio
100 to 120% in 1% steps
DTL delay
0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS
0.010 to 100.000 in 0.001 steps
Reset delay
0.0 to 300.0s in 0.1s steps
Undervoltage block threshold
5.0 to 20.0V in 0.1V steps
Undervoltage block delay
0.00 to 300.00s in 0.01s steps
Under/Over Frequency Protection
1st - 4th under/overfrequency threshold
(Fnom −10.00Hz) – (Fnom −10.00Hz) in 0.01Hz steps
Fnom = nominal frequency
DTL delay:
0.00 – 300.00s in 0.01s steps
Frequency UV Block
40.0 – 100.0V in 0.1V steps
Autoreclose
Number of shots
1 to 5 shots
Dead time for single-phase autoreclose
0.01 to 300.00s in 0.01s steps
Dead time for three-phase autoreclose
0.01 to 300.00s in 0.01s steps
Multi-shot dead line time
0.01 to 300.00s in 0.01s steps
Reclaim time
0.0 to 600.0s in 0.1s steps
Pulse width of reclosing signal output
0.01 to 10.00s in 0.01s steps
Autoreclose reset time
0.01 to 310.00s in 0.01s steps
Reset time for developing fault
0.01 to 300.00s in 0.01s steps
Synchronism check
Synchronism check angle
0° to 75° in 1° steps
UV element
10 to 150V in 1V steps
OV element
10 to 150V in 1V steps
Busbar or line dead check
0 to 150V in 1V steps
Busbar or line live check
0 to 150V in 1V steps
Synchronism check time
0.01 to 100.00s in 0.01s steps
Voltage check time
0.01 to 100.00s in 0.01s steps
Voltage Transformer Failure Supervision
Undervoltage element (phase-to-phase)
50 to 100V in 1V steps
Undervoltage element (phase-to-earth)
10 to 60V in 1V steps
Current change detection element
0.1A fixed (1A rating)
0.5A fixed (5A rating)
Residual voltage element
20V fixed
Residual current element
Common use with earth fault detection element
Fault Locator
Line reactance and resistance setting
0.0 to 999.9
in 0.1
steps (1A rating)
0.00 to 199.99
in 0.01
steps (5A rating)
Line length
0.0 to 399.9km in 0.1km steps
Correction factor of impedance between lines
80 to 120% in 1% steps
Correction factor of impedance between in each
phase
80 to 120% in 1% steps
Accuracy
±0.4km (up to 20km, without fault at near end)
±2% (up to 399.9km, without fault at near end)
Minimum measuring cycles
2.5 cycles
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......