6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 117 -
Switch on to fault (SOTF-OC)
The switch-onto-fault function (SOTF-OC) is used to detect and rapidly clear faults when
circuit breakers (CBs) are closed onto a pre-existing fault in the protected zone. If a circuit
breaker is closed onto a permanent fault, the memory circuit in the IED will be unable to
memorize the voltage data required to retain the pre-fault values. This is because the voltage
input to distance measuring elements is absent continuously prior to and after the fault
particularly with voltage transformers installed on the line side; as a result, the fault cannot
be detected by conventional standard protection functions. Therefore, in order to avoid such
failures, SOTF-OC is applied so that the fault can be detected for a specific period following
the closure of the CB.
─────────────────────────────────────────────────────────────────
Note:
The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see
Appendix: Ordering
.
Table 2.2-1 Comparative table in respective ordering numbers
Sec.
Feature
Ordering No. at “G&T”
31
32
–
Main features
✓
✓
✓
: Applicable NA: Not applicable
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......