6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 327 -
Table 2.23-3 Setting [FL_DIR] corresponding to the setting of OC and other relay elements
Direction of the relay (OC element etc)
Scheme switch [
FL_DIR
]
Forward
Forward
Reverse
Reverse
Non-dir
Forward / Reverse
(iv)
Setting the unit of length/distance
As shown in Figure 2.23-2, the fault location is displayed in kilometers when
km
is set for
scheme switch [
FL_Unit
]. On the other hand, if the preference is to display the fault location
in miles, the user should set
mile
for the scheme switch [
FL_Unit
]. In the case that
km
is set
using scheme switch [
FL_Unit
], the user can apply a value to set the line length using
[
FL_Line_km
]. In the case that
mile
is selected in setting [
FL_Unit
], the value of setting
[
FL_Line_mile
] is used to apply the line length value.
(v)
Setting of FL execution
The FL computation is ready when
On
is set for setting [
FL_EN
].
(vi)
Computation for overreaching
If the user wishes to obtain the result of the FL computation when the fault occurs beyond the
boundary defined with the setting [
FL_Line_km
] or [
FL_Line_mil
e], the result can be displayed
when
On
is set for setting [
FL_ALL_Zone
]. Note that the fault location will be displayed by
On
being set for the [
FL_ALL_Zone
], but the result for overreaching cannot be guaranteed in the
FL computation; thereby, it must be taken carefully.
(vii)
Compensation for earth faults on parallel lines
When applied to parallel lines the FL computation for earth faults is compensated by
introducing the residual current (3I0) from the adjacent line. The residual current is used to
compensate the input current when the earth fault occurs. It is also possible to compensate the
input current using the source-impedance if the residual current on the adjacent line is not
available. Note that this form of compensation is only used when I0m cannot be introduced
from the parallel line.
We recommend that the input current be compensated using the residual current from
the adjacent line; compensation using the residual current improves the accuracy of the FL
computation. (Set scheme switch [
FL-Z0B
] to
Off
)
If the residual current of the adjacent line is not available, the user should set the scheme
switch [
FL-Z0B
]
On
so that the FL result is compensated using the zero-sequence source-
impedances for an earth fault. Table 2.23-4 summarizes the compensation methods provided
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......