- 39 -
Number of zones
The distance protection for phase-to-phase faults (ZS) includes six measuring zones and these
are termed Z1S, Z1XS, Z2S, Z3S, Z4S and Z5S. The distance protection for single-phase-earth
faults (ZG) also includes six measuring zones that are similarly termed Z1G, Z1XG, Z2G, Z3G,
Z4G and Z5G.
Z3S-R.Reach
X
Z3S-R.Angle
Z1XS
–Z5S Mho with impedance Z
Z3S-Mho.Reach
Z1XS
Z2S
Z3S
R
Z5S-Mho.Angle
Z4S
Z5S
Z1S
Z5S-R.Angle
Z5S-R.Reach
Figure 2.1-14 Composition feature for Mho characteristic
Selection of Forward, Reverse, or Non-directional for the respective zones
The selection of the element direction is provided with the setting [
Z*S-Dir
]. For instance, if
Forward
is set, then Z*S is set in forward direction, as shown in Figure 2.1-11 to Figure 2.1-13.
If
Reverse
is set, then Z*S is set in reverse direction, as shown in Figure 2.1-15 to Figure
2.1-17. Z*S can be set non-directional by setting
NonDir
, as shown in Figure 2.1-18 and Figure
2.1-19. The other elements can be set in a similar manner.
Elements in the reverse direction of ZG are not drawn in Figure 2.1-15 to Figure 2.1-17,
but they are similar to the ZS elements.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......