6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1412 -
(PIXIT Ed.1&Ed.2)
15.
PIXIT FOR TIME AND TIME SYNCHONISATION MODEL
ID
Ed
Description
Value / Clarification
Tm1
1
What time quality bits are supported (may be
set by the IED)
Y
LeapSecondsKnown
N
ClockFailure
Y
ClockNotSynchronized
Tm2 1,2
Describe the behavior when the time server(s)
ceases to respond
What is the time server lost detection time
On one time server: IED tries to
synchronize with another time
server.
On all time servers:
The quality attribute
“ClockNotSynchronized” will be set
to TRUE.
The lost detection time depends on
the network condition.
Tm3 1,2
How long does it take to take over the new time
from time server
10 seconds
Tm4 1,2 When is the time quality bit “ClockFailure” set RTC is out-of-order
Tm5 1,2
When is the time quality bit “Clock not
Synchronized” set
It depends on the condition of
synchronization. Typically from 1 to
10 minutes.
Tm6
-
Is the timestamp of a binary event adjusted to
the configured scan cycle
Deprecated
Tm7
1
Does the device support time zone and daylight
saving
Yes for both.
Tm8 1,2
Which attributes of the SNTP response packet
are validated
Y
Leap indicator not equal
to 3?
N
Mode is equal to SERVER
N
OriginateTimestamp is
equal to value sent by the
SNTP client as Transmit
Timestamp
Y
RX/TX timestamp fields
are checked for
reasonableness
Y
SNTP version 3 and/or 4
N
other (describe)
Tm9 1,2
Do the COMTRADE files have local time or
UTC time and is this configurable
UTC
Not Configurable
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......