6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 695 -
&
V1
V2
DS1
DS2
CB1
DS1 closed
DS2 closed
Busbar#1
S43P logic programmed
by the user
Busbar#2
Selection of SYNCHK_Ry1
SYNC01_RY1_USE_STS
SYNCHK01 and 02 functions
✔
Figure 4.6-19 Bus-bar arrangement and PLC setting
Voltage selection should be considered in accordance with the arrangement of VTs.
Voltages V1 and V2 represent the running voltage (VR) and the incoming voltage (VI),
respectively. Consequently,
V-L1
and
V2-L1
are set for the scheme switches [
SyncRy1-VR
] and
[
SyncRy1-VI
], respectively. Table 4.6-8 shows the setting example for this arrangement.
Table 4.6-8 Setting example
Setting Name
Description
Default
Setting item or value
SyncRy1-VR
Selection of running voltage
V-L1
Either of V-L1 / V-L2 / V-L3
SyncRy1-VI
Selection of incoming voltage
V2-L1
Either of V2-L1 / V2-L2 / V2-L3
SyncRy2-VR
Selection of running voltage
N.A
N.A
SyncRy2-VI
Selection of incoming voltage
N.A
N.A
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......