6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 723 -
(iii)
Receiving “Select command On” from the local-end
Figure 4.8-5 outlines the reception of the Select command ‘On’ from the local-end.
Signal reception
from the front panel
Select command On from the local-end
Signal output
Select
decision
Success
Failed
Select logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Off from the remote-end
Select command Off from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Select command On from the remote-end
Figure 4.8-5 Outline of Select command ‘On’
Input signal generated at the local-end
Figure 4.8-6 shows the Select logic when “Select command On (Local-ON-Control)” signal is
applied to the DPOS01 function. The signal is provided when an “On” key is pressed on the
IED front panel; the user is not required to take account of mapping. Note that the user should
set the scheme switch [
DPOS01-CTRAHMI
] to
SBO
when operation from the IED front panel
is required, we discuss how to set this in chapter
User interface: Control sub-menu
.
Output signal to BO
When the “select condition” signal is true, the DPOS01 function can issue a “Select success”
signal at the output-point “DPOS01_OSL_BO_CSF”.
Note: The “DPOS01_OSL_BO_CSF” signal is the same as the signal shown in Figure
4.8-2. If the input signal “Local-ON-Control” is not true, the DPOS01 function
returns to the “Wait for a command” stage.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......