6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 931 -
Typical pick up level
Guaranteed pick up level
Guaranteed drop off level
Operating area
Intermediate area
Non-operating area
Input voltage
Figure 5.4-2 Operating area in the variable type
Note: In practice, the pick-up voltages depend on respective binary circuits physically
This means the characteristics are not affected by the ambient conditions and the
applied voltages.
(ii)
Comparison feature for contact chatter
The input circuit incorporates a comparison feature that protects against contact chatter and
this feature is configured using the setting [
CMP_NUM
]. Figure 5.4-3 illustrates this feature;
the comparison feature removes contact chatter.
The period ‘
t
’ applied for the removal of contact
chatter can be configured by setting a value for [
CMP_NUM
].
The formula for the calculation
of ‘t’ is,
[
CPM_NUM
]×
1
System Frequency×12
The setting [
CMP_NUM
] is provided for all binary input circuits.
Figure 5.4-3 Chattering countermeasure (e.g. [CMP_NUM] = 4)
Actual input signal
Imported signal by
binary input circuit
t
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......