6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 437 -
3.3.1
Control level and control point
As shown in Figure 3.3-1, the control hierarchy is distributed across three levels; the network
level having a remote-control center (RCC); the station level having operator and engineering
work stations (OWS/EWS); and the bay level† having an IED equipped with an LCD screen.
One of the three control-points (RCC, OWS/EWS, and LCD) is available to issue a control-
command.
†Note: We, hereafter, discuss only the operations at the bay level; that is, we focus only
on operations made from the bay level. The scope of this discussion does not
include operations from either the remote control center or the network levels.
3.3.2
Selector switches and bay operations
At the bay level, the 43BCU switch opens a path to permit the flow of the control-right.
(i)
LCD operation
When the user sets the 43BCU switch to “
Local
(
L
)”, the issuing of a control-command from
the LCD is possible for the device.
(ii)
RCC, EWS, or OWS operation
Alternatively, suppose that the position “
Remote
(
R
)” is selected at the 43BCU switch. In this
case, the issuing of the control-command from the LCD is not possible.
3.3.3
Programming of control-right distributions
Figure 3.3-2 illustrates that the PLC function provides the means to distribute the control-
right for the control functions.
The part
○
1
and
○
2
logics are programmed so that, the control-right signal can be
distributed to the respective control applications. With regard to the DPSY01 function, PLC
connection point “DPSY01IN_TMP_28” has been programmed using DOUT_BOOL feature (for
example). Therefore, the control-right signal is transferred to the select and operate-condition
logic‡ when the user connects the control-hierarchy with the DPSY01 function using
“DPSY01IN_TMP_28”.
‡Note: The select-condition and operate-condition logic are used to decide upon the
execution of a select command or an operate command in the DPSY01 function.
For more detail, see chapter
Control and monitoring application: DPSY function:
Operate condition and Select condition. As per the DPSY function, other functions,
such as SPOS, DPOS, and TOPS, have the same logic; the user is required to do
the connection.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......