Signal
Signal monitoring points in ASEQ01
ASEQ(Function ID: 523001)
Element ID
Name
Description
000D001F40
ASEQ_MULTI_SEL
Status flag to not be selected for multiple operations
000D011001
ASEQ01_ACC_EXEC
Reception state of the automatic sequence instruction command
000D011D90
ASEQ01_STSELD
ASEQ01 selected signal(stSeld) for SAS
310D011D00
ASEQ01_MMC_ST
ASEQ01 state for MIMIC
310D011D01
ASEQ01_LCD_ST
ASEQ01 state for LCD
800D011D51
ASEQ01_SC_OWS
ASEQ01 select command by OWS(HMI)
800D011D52
ASEQ01_SC_RCC
ASEQ01 select command by RCC
800D011D53
ASEQ01_SC_RMT
ASEQ01 select command by Remote
800D011D54
ASEQ01_SC_LCD
ASEQ01 select command by LCD
800D011D55
ASEQ01_EC_OWS
ASEQ01 execute command by OWS(HMI)
800D011D56
ASEQ01_EC_RCC
ASEQ01 execute command by RCC
800D011D57
ASEQ01_EC_RMT
ASEQ01 execute command by Remote
800D011D58
ASEQ01_EC_LCD
ASEQ01 execute command by LCD
810D011F51
ASEQ01_EXEC_STOP
Commencing command for automatic sequence
820D011F50
ASEQ01_EXEC_START
Stop command for automatic sequence
000D0D1001
EMERSTOP_ACC_EXEC
Reception state of an emergency signal to stop the operation
000D0D1D90
EMERSTOP_STSELD
EMERSTOP selected signal (stSeld) for SAS
310D0D1D00
EMERSTOP_MMC_ST
EMERSTOP state for MIMIC
310D0D1D01
EMERSTOP_LCD_ST
EMERSTOP state for LCD
800D0D1D51
EMERSTOP_SC_OWS
EMERSTOP select command from OWS(HMI)
800D0D1D52
EMERSTOP_SC_RCC
EMERSTOP select command from RCC
800D0D1D53
EMERSTOP_SC_RMT
EMERSTOP select command by Remote
800D0D1D54
EMERSTOP_SC_LCD
EMERSTOP select command from LCD
800D0D1D55
EMERSTOP_EC_OWS
EMERSTOP execute command from OWS(HMI)
800D0D1D56
EMERSTOP_EC_RCC
EMERSTOP execute command from RCC
800D0D1D57
EMERSTOP_EC_RMT
EMERSTOP execute command by Remote
800D0D1D58
EMERSTOP_EC_LCD
EMERSTOP execute command from LCD
810D0D1F50
EMERSTOP_EXEC_STOP
Commencing command for emergency stop
Connection points in PLC logic in ASEQ01
ASEQ(Function ID: 523001)
Element ID
Name
Description
820D01ED50
ASEQ01IN_TMP_28
Reception of control right for ASEQ01
800D01EDF2
ASEQ01_EXEC_RESET
Reception of reset signal for ASEQ01 operation
820D10ED50
EMERSTOPIN_TMP_28
EMERSTOPIN_TMP_28
Mapping point in ASEQ01
ASEQ(Function ID: 523001)
Element ID
Name
Description
700D016D08
ASEQ01_CONTROL_REQ
ASEQ01 control command received. (Mapping Data)
Note: In the table above, the user will only find Element IDs and their names for the 1
st
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......