6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 880 -
4.11.6
Mapping for IEC61850 communication
The user can operate the ASEQ function using IEC 61850 communications after first
completing the appropriate mapping using the GR-TIEMS software. Note that the ASEQ01
function is designed for the “Single Point Controller (SPC) class” described in the IEC 61850
communications standard. The user should follow steps:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data
(i)
Editing Logical Node
The user should implement a logical node (LN) for the ASEQ01 function. Figure 4.11-5
exemplifies LN editing; the LN “(GAPC1)” is chosen for the ASEQ01 function. After the user
has defined an object “SPCSO1”, the ASEQ01 logical node is saved with the name “SPCSO1”
plus “LN Instance”. A definition for the object “SPCSO1” is made in the ASEQ01 logical node.
Choose either the SBO mode or the DIR mode when editing the LN.
SBO defined in LN
Figure 4.11-5 Defining “SPCSO1” object in GAPC1 logic node
Defining SBO mode
Figure 4.11-6 exemplifies the settings in LN “GAPC1” when the SBO mode is required for the
ASEQ01 function. In SBO control, the user should select the following items for the object
reference “GAPC1$SPCSO1” using the GR-TIEMS software;
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......