6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 881 -
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down
Figure 4.11-6 LN editing screen for SBO mode (for example)
Defining DIR mode
Figure 4.11-7exemplifies the settings in LN “GAPC1” when the DIR mode is required for the
ASEQ01 function. In the DIR mode, the following three items should be selected using the GR-
TIEMS software:
Oper
Origin
ctlmodel (choice ”DOes or DOns”)
Figure 4.11-7 LN editing screen for DIR mode (for example)
(ii)
Mapping output data
The user should group the ASEQ01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS.
Table 4.11-11 shows the signals in the ASEQ01 function that require mapping to the IEC
61850 communications. Figure 4.11-8 shows how to map a signal.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......