6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 461 -
3.6.5
Mapping for IEC61850 communication
The user can operate the LEDR function over IEC 61850 communication following mapping
using GR-TIEMS. Note that the LEDR function is designed for “LEDRs” in the IEC 61850
standard for communication. The user should follow these steps, each of which is discussed
below:
Step1:
Editing Logical Node
Step2:
Mapping output data
Step3:
Mapping input data
(i)
Editing Logical Node
The user will need to create a logical node (LN) for the LEDR function. Figure 3.6-10
exemplifies the editing of a LN; the LN “logical node zero (LLN0)” is chosen for the LERD
function. Either the SBO mode or the DIR mode should be chosen in the editing for the LN.
SBO defined in LN
Figure 3.6-10 Defining “LEDRs” object in LLN0 logic node
Defining SBO mode
Figure 3.6-11 exemplifies the LEDR logic node saved as “LLN0”. In the SBO mode, the user
should select the following items in the “LLN0$LEDRs” using GR-TIEMS:
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......