6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1095 -
10.2.22
Supervision of binary IO module#4 (BIO#4 error)
A supervision function is provided to detect the operation failure in the forth binary IO modules
(BIO)†.
†Note: The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.
(i)
Error level
Generally, the error level has been set at level 1 (
Serious error
1
), as default. For example, the
user can program the level using setting [
CHK_BIO4:LVl
] when the BIO module at the IO#4
2
slot should be supervised; then, set
On
for the setting [
CHK_BIO4:Sw
]. The manufacture sets
one (1) second to detect the failure; it is reset in a second when the failure is cleared.
1
Note: The entire operation of the IED is stopped forcibly when the error is detected.
2
Note: The location of the IO slot is discussed in Chapter
Technical description: IED case
and module slot.
(ii)
Error message
When detecting an error, an error message can be shown on the LCD screen and an LED is lit.
Table 10.2-45 Error messages provided by the supervisor in CHK_BIO4
Message and level
Meaning of the information
BIO#4 error
Detection of the BIO failure at IO slot#4
Error level
Serious error (Level 1)
Table 10.2-46 Detailed information in Hexadecimal in CHK_BIO4
Display
area
Meaning of the detailed information
Left column
Right column
Top
row
00000001: CRC error
00000002: Connection error
00000004: Read back error
Count number by the CRC error
Middle
row
Count number by the connection error
Count number by the read-back error
Bottom
row
(No message displayed)
(No message displayed)
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......