6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 539 -
Signal Number
Signal Name
Description
510001 8101141DD0
SPOS20_FEX_BO
SPOS20 operate (OFF) command for Binary Output.
(v)
Setting names
Note: The “xx” of “SPOSxx” represents the SPOS function number. (e.g., if the SPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented from
“01” to “20”.)
Table 4.1-28 Settings for Binary input signals in SPOSxx
Setting Name
Description
Default
Setting item or value
SPOSxx-EN
Activate monitoring function of SPOS01-20
On
Off / On
SPOSxx-NOPSG
BI position for SPOS01-20
*none
BI signal
SPOSxx-SPPEN
Activate event suppression for SPOS01-20
On
Off / On
SPOS-NELD
Number of change to lock status
10
0~99
SPOS-TELD
Time to lock status( sliding window )
10[sec]
1~99[sec]
SPOS-TELR
Time to unlock status( sliding window )
10[sec]
1~99[sec]
Table 4.1-29 Settings for health check function in SPOSxx
Setting Name
Description
Default
Setting item or value
SPOSxx-SLBORD
Select BO signal (BO*-RB) from signal list
*user-preferred
BO readback signal
SPOSxx-OEXBORD
Select BO signal (BO*-RB) from signal list
*user-preferred
BO readback signal
SPOSxx-FEXBORD
Select BO signal (BO*-RB) from signal list
*user-preferred
BO readback signal
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......