6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 406 -
Provision of trigger signals to Recording functions
The ‘TRIP COMMMAND1-A, -B, -C’ and ‘TRIP COMMMAND2-A, -B, -C’ signals are viable to
operation of Recording function, which we shall see in Chapter
Recording function
.
Provision for distance relay
The ‘GEN.TRIP’ signal is provided to direct the operation of the UVPWI relay in the distance
protection function, which we shall see in Chapter
Relay application: Distance protection
.
(iii)
CB trip signal production
As illustrated in Figure 2.26-3, the ‘TRIP COMMMAND1-A, -B, -C’ and ‘TRIP COMMMAND2-
A, -B, -C’ signals are transferred to trip coils of the CB#1 and CB#2 when the signals “OPT-
TRIP-A, -B, and -C” or “OPT-TRIP” enter into the TRC function.
CB trip signals for 1CB system
When the TRC function operates in a single CB (1CB) system; the “TRIP COMMMAND1-A, -
B, -C” signals should be connected with BO circuits.
Table 2.26-7 Output signals for single CB#1
Output signals
Usage of signals
TRIP-COMMMAND1-A
CB trip in phase A
TRIP-COMMMAND1-B
CB trip in phase B
TRIP-COMMMAND1-C
CB trip in phase C
CBs trip signals for 1.5CB system
When the TRC function can operate in a single-and-a-half breaker system (1.5CB); the other
“TRIP COMMMAND2-A, -B, -C” signals also should be connected with other BO circuits. Table
2.26-8 summarizes the outputs signals of the TRC function in the 1.5CB system.
Table 2.26-8 Output signals for CB#1 and CB#2 in 1.5CB system
Output signals
Usage of signals
TRIP-COMMMAND1-A
CB#1(Bus CB) trip in phase A
TRIP-COMMMAND1-B
CB#1(Bus CB) trip in phase B
TRIP-COMMMAND1-C
CB#1(Bus CB) trip in phase C
TRIP-COMMMAND2-A
CB#2(Center CB) trip in phase A
TRIP-COMMMAND2-B
CB#2(Center CB) trip in phase B
TRIP-COMMMAND2-C
CB#2(Center CB) trip in phase C
(iv)
Sub-signal generation
In a similar way to the Trip-signal collection, the Sub-signal generation groups the blocking
signals for ARC operation; it groups them into ‘GEN.ARC-BLOCK’ signal, as illustrated in
Figure 2.26-4. Blocking signal from the CBF function is also integrated into the ‘GEN.ARC-
BLOCK’ signal; then it is transferred to the ARC function.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......