6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 585 -
(i)
Receiving “change value for counter” from the remote end
Mapping of Input point required
Figure 4.2-34 depicts the logic when a “change value for counter” command is received at the
DPSY01
logic.
With
regard
to
a
three-phase
counter,
the
input-point
“DEV01_3PH_CONTROL_REQ” is used. With regard to a phase-A counter, the input-point
“DEV01_APH_CONTROL_REQ” is used. For phase-B and phase-C, the input-points
“DEV01_BPH_CONTROL_REQ” and “DEV01_CPH_CONTROL_REQ” are used.
DPSY01 function (Function ID: 511001)
Operate Command
DEV01_3PH_REQ
Command
“change value for counter”
511001
_
7002016D09
&
“DPSY01_SLD_CSCN”
(511001 8A02011F88)
Input
Output
Operate logic in DPSY01
Operate condition
‡
Figure 4.2-34 Change counter value for three-phase
†
with operation from the remote-end in
DPSY01
‡Note: The “operate condition” signal is provided from the operate condition logic shown
†
Note: The user can apply other counter change commands for phase-A, -B, and –C as
shown in Table 4.2-24. The resultant signals for the DPSY02 logic are shown in
Output signal to BO
The DPSY01 function can issue a “Result” signal at output point “DPSY01_SLD_CSCN”. The
counter values are issued at points “DPSY01_CNT_VAL", “DPSY01A_CNT_VAL",
“DPSY01B_CNT_VAL", and “DPSY01C_CNT_VAL".
(ii)
Receiving “change value for counter” from the local-end
Input signal from the front panel
Figure 4.2-35 depicts the logic when a “change value for counter” command is provided in the
DPSY01 function. The command is provided from the sub-menu (see Figure 4.2-33).
DPSY01 function (Function ID: 511001)
“DPSY01_SLD_CSCN”
(511001 8A02011F88)
Input
Output
Operate logic in DPYS01
Command
“Change value”
Figure 4.2-35 Changing counter value by operation from the front panel in DPSY01
Output signal to BO
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......