4.2.4
Operation counter
The DPSY01 function has an operation-counter†; the user can utilize the operation-counter to
predict the lifespan of switchgear and other functions. The user can select a count mode using
a setting. Table 4.2-23 and Figure 4.2-32 show the modes for which a user is required to change
a mode in response to a device signal. For instance in the DPSY01 function, a user can select
the mode using scheme switch [
DPSY01-CNTS
] ,which is set to
C-On
; counting-up is performed
when a switchgear signal gives rise to a change in state from “Open to Closing”.
Table 4.2-23 Mode of operation counter
Mode
Description
C-On
Counting-up is performed when a signal changes to closed (ON). When the signal
is changed from “Open to Closed”, the counter value is incremented.
C-Off
Counting-up is performed when a signal changes to open (OFF). When the signal
is changed from “Closed to Open”, the counter value is incremented.
C-OnOff
Counting-up occurs when any state change occurs: “Open to Closed” and “Closed
to Open”.
NA
Stops the count function
†Note: The operation-counter value is not cleared when power is removed from the IED.
This counter is available in the DPSY01 and DPSY02 functions.
Closed
Open
Figure 4.2-32 Device Signal
The user can change the value of the operation-counter from either the front panel or
remotely. For example, in the sub-menu for “Operation Counter, the user can set a user-
preferred value for the operation-counter. See Chapter
User interface: Monitoring sub-menu
on how to operate the sub-menu.
DPSY1-CNT1
10:48
1/4
DPSY_Dev1-3Ph +
0
DPSY_Dev1-APh +
0
DPSY_Dev1-BPh +
Operation Counter
10:48
1/25
_DPSY1-CNT
>
DPSY2-CNT
>
DPOS1-CNT
>
DPOS2-CNT
>
DPOS3-CNT
>
DPOS4-CNT
>
ENTER
CANCEL
Figure 4.2-33 Operation counter sub-menu
Note: With regard to the signal “DPSY01_3PH_STATE”, the sub-menu represents it as
“DPSY_Dev1-3Ph”. Analogous to signal “DPSY01_3PH_STATE”, the signal
“DPSY01_APH_STATE” is represented as “DPSY_Dev1-APh”. The signals
“DPSY01_BPH_STATE” and “DPSY01_CPH_STATE” are displayed in a similar
manner.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......