6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 908 -
Setting of AC analog input(Function ID: 200201)
Setting item
Range
U
n
i
t
s
Contents
Default setting
value
Notes
1A
rating
5A
rating
1A
rating
5A
rating
VC1
AI1_Ch1_Rating
DEP / (1A) / (5A)
– Rated current at CH#1
DEP
alpha-numeric
AI1_Ch2_Rating
DEP / (1A) / (5A)
– Rated current at CH#2
DEP
references
AI1_Ch3_Rating
DEP / (1A) / (5A)
– Rated current at CH#3
DEP
AI1_Ch4_Rating
DEP / (1A) / (5A)
– Rated current at CH#4
DEP
AI1_Ch5_Rating
DEP / (1A) / (5A)
– Rated current at CH#5
DEP
AI1_Ch6_Rating
DEP / (1A) / (5A)
– Rated current at CH#6
DEP
AI1_Ch7_Rating
DEP / (1A) / (5A)
– Rated current at CH#7
DEP
AI1_Ch8_Rating
DEP / (1A) / (5A)
– Rated current at CH#8
DEP
AI1_Ch9_Rating
DEP / (1A) / (5A)
– Rated current at CH#9
DEP
AI1_Ch10_Rating
DEP / (1A) / (5A)
– Rated current at CH#10
DEP
AI1_Ch11_Rating
DEP / (1A) / (5A)
– Rated current at CH#11
DEP
AI1_Ch12_Rating
DEP / (1A) / (5A)
– Rated current at CH#12
DEP
AI1_Ch13_Rating
DEP / (1A) / (5A)
– Rated current at CH#13
DEP
AI1_Ch14_Rating
DEP / (1A) / (5A)
– Rated current at CH#14
DEP
Note: Channel numbers for rated settings are dependent on VCT type.
1A
and
5A
are shown above, but neglect them. They are invalid here. Confirm
that all have
DEP
setting from LCD menu or GR-TIEMS screen.
(iii)
Example for VCT12B rated current change
Figure 5.2-6 shows the setting items and corresponding rating jumpers about VCT12B.
VCT jumper: Close or open the circuits named W* numbers corresponding to the
currents. The hatched areas are required to close or open.
For changing to 5A rated, insert jumpers at W6, 7, 8, 12, 13.
For changing to 1A rated, remove jumper at W6, 7, 8, 12, 13.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......