6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 351 -
2.24.4
Timing diagram
(i)
Single shot scheme for an Arcing fault (Shot1 for CB#1 and
successful operation in TPAR mode)
Figure 2.24-5 illustrates an example for which the single shot scheme has been selected (i.e.
[
ARCNUM
]=S1); an arcing fault is cleared following the operation of the protection relay and
the issue of the ‘GEN.TRIP-A/B/C’ signals for the tripping of the CB#1. The ‘GEN.TRIP-A/B/C’
also initiates the ARC function and an ‘ARC1 CLOSE COMMAND’ signal is issued following
the expiration of the dead time set for [
TTPAR1
]. When
On
is set for [
ARC-SucChk
], this
scheme will determine that the ARC1 was successful when the ‘CB1 ALLPH CLOSE’ signal is
detected following the issuing of the ‘ARC1 CLOSE COMMAND’ signal; the operation of the
ARC function is reset if it operates successfully (i.e., the ‘ARC1 IN-PROG’ signal is turned off).
Relay operation
GEN.TRIP
ARC1 IN-PROG
ARC1-S1 IN-PROG
ARC1 SHOT1
Dead Time [
TTPAR1
]
)
ARC1 CLOSE COMMAND
[
TCCW1
]
)
CB#1 status
Closed
Open
ARC1 CLOSE SUCCESS
ARC1 CLOSE FAIL
CB1_ ALLPH_CLOSE
Fault current
ARC1 FT
ARC1-S2 IN-PROG
ARC1 SHOT2
ARC1-S3 IN-PROG
ARC1 SHOT3
20ms
)
Operated
Issued
Closed
Figure 2.24-5 Single shot scheme [ARC-NUM]=S1 for an Arcing fault; operation is successful
Note: The permissive signal ‘ARC1-VCHK’ is required in the TPAR mode, but is omitted
here for the sake of clarity. The pulse width of the ‘ARC1 CLOSE COMMAND’
signal is defined using the setting [
TCCW1
].
(ii)
Single shot scheme for an Arcing fault; CB#1 fails to reclose
Figure 2.24-6 also shows the single shot scheme. However, the CB#1 fails to reclose on
receiving the ‘ARC1 CLOSE COMMAND’ so that the ARC function initiates the ‘ARC1 CLOSE
FAIL’ signal within the setting time [
TARCDSUC
]. Consequently, the ARC function goes to the
final trip (ARC1 FT) stage so that the ARC will not issue another ‘ARC1 CLOSE COMMAND’
signal hereafter.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......