6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 762 -
4.8.5
Measurement of operation intervals
The DPOS01 function can measure operation intervals (OT1 to OT4) †; the intervals OT1 to
OT2 can represent the period of time when a switch changes from “Closed” to “open”. In the
DPOS01 function the operation period is grouped into sub-time periods, as shown in Table
4.8-26. The user should set scheme switch [
DPOS01-OPETMEN
] to
On
.
Table 4.8-26 Four intervals measured in DPOS01 function
Intervals
Trigger Events for measurement
OT1
Start
Signal “DPOS01_FEX_BO” sensed
End
Switch status is changed from “On” to
“Intermediate”
OT2
Start
Device status “Intermediate” sensed
End
Switch status is changed from “Intermediate” to
“Off”
OT3
Start
Signal “DPOS01_OEX_BO” sensed
End
Switch status is changed from “Off” to
“Intermediate”
OT4
Start
Device status “Intermediate” sensed
End
Switch status is changed from “Intermediate” to
“On”
†Note: The function “operation time measurement” is available in the DPOS01 to
DPOS72 functions.
Signal “DPOS01_FEX_BO”
OT1
OT2
Sensing
intermediate state
Device status for Off
On
Intermediate
Off
Figure 4.8-37 Two intervals (OT1 and OT2) for Off-control
Signal POS01_FEX_BO”
OT3
OT4
Off
Intermediate
On
Sensing
intermediate state
Device status for On
Figure 4.8-38 Two intervals (OT3 and OT4) for On-control
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......