6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 821 -
this signal is now generated by the user-programmed logic at connection point#2
“User configurable condition”. That is, set the scheme switch [
TPOS01-
LGP1EXOT
] to
PLC
and use “TPOS01IN_TMP_38”.
††
Note: To identify the input and output signals of the other TPOS logics, see Table
4.9-16 for PLC#2, Table 4.9-17 for PLC#3 and Table 4.9-20 for the outputs.
Output signal to BO
The TPOS01 function, in Figure 4.9-35, can issue an “Operate” signal at the output point
“TPOS01_P2EX_BO”, when the TPOS01 function determines that the “Local-P2-Control”
signal is true.
(vi)
Receiving “operate command P3-control” from the local-end
Figure 4.9-36 depicts the reception of the operate command ‘P3-control’ from the local-end.
Signal reception from
front panel
P3 control from the local-end
Do nothing
Operation
decision
Success
Failed
Operate logic
P1 control from the remote-end
P2 control from the remote-end
P3 control from the remote end
P1 control from the local-end
P1 control by the PLC function
P2 control from the local-end
P2 control by the PLC function
Wait for a command
P3 control from the local-end
P3 control by the PLC function
Select logics
Signal output
P3 control from the remote end
P1 control from the local-end
P1 control from the remote-end
P2 control from the remote-end
P2 control from the local-end
P1 control by the PLC function
P2 control by the PLC function
P3 control by the PLC function
Wait for a next command
Figure 4.9-36 Outline of Operate command ‘P3-control’
Input signal generated at the local-end
Figure 4.9-37 illustrates the operate logic when an “Operate command P3 (Local-P3-Control)”
signal is applied to the TPOS01 function. The input signal is provided when “P3-control” is
keyed on the IED front panel.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......