In cases where CTs are specified as P-class protective current transformers
according to IEC 60044-1 (e.g. 5P10, 5P20 etc.), the knee point voltage can be
approximated as follows:
Vk 0.8 × n × In × (Rct + RVA)
where,
Vk: Knee point voltage.
In:
Rated current at secondary CT.
Rct: Resistance of CT.
RVA: Rated burden.
n:
Accuracy limiting factor of CT (e.g. 20 for 5P20)
(All values refer to the CT secondary side)
3.
Remanent flux has not been considered. In cases where a high level of remanent
flux may be experienced, it may be necessary to include an additional margin
when dimensioning the CT.
4.
The data provided is valid for 50Hz and 60Hz power systems.