background image

The JA-80S wireless fire detector 

 

MHS51505 

 

The JA-80S wireless fire detector  

 

This device is designed to detect the presence of fire inside residential or 

commercial buildings. It should not be installed in industrial premises. The battery-

powered detector has a built-in local warning siren combined with a red LED 

indicator. Alarm information can also be transferred 

via a wireless connection to 

OASiS systems.  

The JA-80S detector combines an optical smoke sensor with a heat sensor. Both 

sensors have their outgoing signals processed digitally, resulting in higher false 

alarm immunity. The optical sensor works using a light diffusion principle and is 

very sensitive to the presence of large-sized particles which are characteristic of 

dense smokes. By contrast, the sensor is less sensitive to small-sized particles 

which are typical of cleanly burning fires. In particular, the smoke sensor is not 

capable of detecting the by-products of cleanly-burning fluids such as alcohols, for 

instance.  This deficiency is compensated for by the built-in heat sensor. This 

sensor provides a slower reaction when compared to the smoke sensor, but is 

much better at reacting to fires with rapidly rising heat producing only a little smoke. 

Smoke / heat sensor participation is configurable by jumper-settings.  

 

Detection range, detector positioning 

The smoke detector must be installed so that any smoke easily drifts into the 

detector, such as on the ceiling. It is suitable for residential buildings, but not 

suitable for free spaces or an outdoor environment. 

However, the detector is not 

suitable for installation in outdoor spaces or interiors with an extremely high ceiling 

(more than 5 m) where fire by-products would not reach the detector position.

 

The detector must always be placed in the section leading to the exit of the 

apartment (escape route), see Figure 1. If the apartment has a floor area greater 

than 150 m

2

, an additional detector is required in the apartment, see Fig.2. 

An apartment block must be equipped with a detector in each apartment. In 

family houses and residential flats or maisonettes a detector must also be placed 

at the highest point of common hallways or spaces (escape routes), see Fig.3. 

KITCHEN

MINIMUM SECURITY
FOR MORE SECURITY

LIVING ROOM

BEDROOM

BEDROOMS

 

 

Fig. 1 

BEDROOMS

BEDROOM

BEDROOM

LIVING ROOM

KITCHEN

MINIMUM SECURITY
FOR MORE SECURITY

 

Fig. 2 

It is recommended to place 

additional detectors in rooms where 

people sleep or in rooms with an 

increased risk of fire, see Fig.2.  

 

Positioning on level ceilings

 

Place the detector in the center of 

the room, as level as possible. 

Detectors must not be recessed into 

the ceiling (worse conditions for the 

spread of smoke). Never place the 

detector in a room corner (ensure a 

distance of at least 0.5 meters from 

the corner), see Fig 4. 

BED

ROOM

KITCHEN

MINIMUM SECURITY

BED

ROOM

BED

ROOM

 

Fig. 3 

   Installation on sloping ceilings 

If the ceiling is not suitable for mounting on a level surface (e.g. a room under a 

roof ridge), the detector can be installed as in Figure 5. 

 

0.5m

CEILING

BEST LOCATION

(CENTRE OF CEILING)

ACCEPTABLE 

LOCATION

 

Fig. 4 

90cm

 

 

Fig. 5 

  Walls, partitions, barriers and lattice ceilings 

The JA-80S 

must not be installed closer than 0.5 m from any wall or partition

. A 

narrow room with a width of less than 1.2m requires the detector(s) to be placed at a 

distance of at least one third of the room’s width away. In the case of separating walls 

(partitions, warehouse objects) which do not reach the ceiling, the space is 

considered 

to be fully separated if the gap between the top of the separating wall and the 

ceiling does not exceed 0.3 m

.  A free space of at least 0.5m is required under the 

detector. Irregularities in ceiling shape which do not

 exceed 5% of ceiling height are 

considered insignificant – the ceiling can be regarded as being even and limits from 

the table are 

applicable. 

However, any irregularity (including beams) exceeding 5% 

of the ceiling height is considered to be a wall with the consequences stated 

above

  Ventilation and air circulation 

The detectors must not be installed directly by a fresh air inlet

, e.g. air 

conditioning vents. In the case of air being supplied through a perforated ceiling, each 

detector must be placed so that no perforation hole occurs within 0.6m of the detector. 

  Avoid installing the detector in the following locations: 

  Places with poor air circulation (niches, corners, apexes of A-shaped roofs). 

  Places exposed to dust, cigarette smoke or steam. 

  Places with over-intense air circulation (close to ventilators, heat sources or air 

conditioning outlets). 

  Kitchens and other cooking places (because steam, smoke or oily 

fumes can reduce detector sensitivity). 

 

Beside lights (electrical interference can cause a false alarm)

 

 

Areas with lots of small insects

 

 

Caution: Most false alarms are due to detector misallocation 

See CEN/TS 54-14 standards for detailed installation guidelines. 

 

 

Installation 

1.  Open the detector by turning the rear cover to the left and remove the battery 
2. 

Screw the rear cover

 onto the desired location  

3. 

Set the required function

 using the jumpers

 

– see the table below 

4.  Please read the receiving device (control panel) installation manual before you connect the 

battery (remove the insulation tape) and set the control panel to enrollment mode  

5.  When the battery is connected, the detector sends a signal to connectto the system  
6.  After installing the detector, allow approx. 20 seconds for stabilisation. This 

period is indicated by the LED being continuously lit and is 

followed by an 

auto-test

. Successful performance of the auto-test is 

confirmed acoustically.

 

 

op

en

clos

e

LI

TH

IU

M

 3

,6

A

A

TEST

1

 

 

ON 

INSTANT alarm mode 

OFF 

Smoke (EN 14064)  

or heat (EN 54-5) 

OFF 

FIRE alarm mode 

OFF 

ON 

Memory ON  

ON 

Only smoke (EN 14604) 

(heat indifferent) 

OFF 

Memory OFF 

OFF 

1

1 2 3 4

 

ON

OFF

 

OFF 

Only heat (EN 54-5) 

(smoke indifferent) 

ON 

ON 

Smoke and heat 

(both simultaneously) 

ON 

 

 

Testing the detector is automatically performed up to 10 secs after 

battery insertion. New settings are saved directly afterwards. 

 

J1:

 The 

FIRE / INST

 alarm mode jumper sets the reaction of the system. FIRE 

= alarm is triggered even if the system is disarmed while INST = alarm is 

triggered only in an armed system. The 

FIRE / INST

 jumper only has an effect if 

the detector has a natural reaction assigned to its address in the Oasis control 

panel.  It also has no effect when used with a UC-8x or AC-8x receiver.  

Warning:  In the INST position, while the system is disarmed, it is not 

protecting against fire.  This setting also fully disables the optical and 

acoustic indication on the detector itself. 

J2: Alarm memory:

 

If the event memory is ON at the time of alarm, alarm LED 

indication continues even if normal conditions are restored. The indication can be 

stopped by pressing the button (indication is valid only for FIRE settings).  

J3 and J4: Smoke / heat sensor participation 

Optical smoke sensor

: Smoke entry into the detector is indicated as a pre-alarm 

state by the LED flashing. If the smoke threshold density is exceeded, a siren 

sound is generated (indication is valid only for FIRE settings). 

Heat sensor:

 indication logic is equal to that of the smoke sensor. 

Whenever the detector cover is opened, a tamper signal is sent. 

 

 

 

   Testing the detector  

The functioning of the detector can be tested by pressing and holding the test 

button (e.g. for 1 sec).  This activates the siren and the LED flashes (LED only if 