6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 774 -
(v)
Signal name and number
Table 4.8-32 PLC monitoring points (Output signal for event suppression function in DPOSxx)
Signal Number
Signal Name
Description
512001 3103011001
DPOS01_3PH_STATE
DPOS01 3ph_state
512001 3103021001
DPOS02_3PH_STATE
DPOS02 3ph_state
512001 3103031001
DPOS03_3PH_STATE
DPOS03 3ph_state
….
….
….
512001 3103481001
DPOS72_3PH_STATE
DPOS72 3ph_state
512001 8103011F5F
DPOS01_F_QLT_SPP
Event suppression detected (DPOS01)
512001 8103021F5F
DPOS02_F_QLT_SPP
Event suppression detected (DPOS02)
512001 8103031F5F
DPOS03_F_QLT_SPP
Event suppression detected (DPOS03)
….
….
….
512001 8103481F5F
DPOS72_F_QLT_SPP
Event suppression detected (DPOS72)
(vi)
Setting names
Note: The “xx” of “DPOSxx” represents the DPOS function number. (e.g., if the DPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented as “01”
to “72” for control (monitor).
Table 4.8-33 Setting for Binary input signals in DPOSxx
Setting Name
Description
Default
Setting item or value
DPOSxx-CTREN
Activate control function of DPOS01-72
On
Off / On
DPOSxx-CTRAHMI
Activate local panel control of DPOS01-72
SBO
DIR / SBO
DPOSxx-EN
Activate monitoring function of DPOS01-72
On
Off / On
DPOSxx-DEVTYPE
Selection of device type
3-pole
3-pole/1-pile/ switch
DPOSxx-OPC
Activate monitoring function of DPOS01-72
On
Off / On
DPOSxx-CPC
Activate monitoring function of DPOS01-72
On
Off / On
DPOSxxA-NOPSG
BI position for DPOS01-72
*none
BI signal
DPOSxxA-NCLSG
BI position for DPOS01-72
*none
BI signal
DPOSxxB-NOPSG
BI position for DPOS01-72
*none
BI signal
DPOSxxB-NCLSG
BI position for DPOS01-72
*none
BI signal
DPOSxxC-NOPSG
BI position for DPOS01-72
*none
BI signal
DPOSxxC-NCLSG
BI position for DPOS01-72
*none
BI signal
DPOSxx-SPPEN
Activate event suppression for DPOS01-72
On
Off / On
DPOS-NELD
Number of change to lock status.
10
0~99
DPOS-TELD
Time to locking state( sliding window )
10[sec]
1~99[sec]
DPOS-TELR
Time to unlocking state (sliding window )
10[sec]
1~99[sec]
Table 4.8-34 Setting for health check feature in DPOSxx
Setting Name
Description
Default
Setting item or value
DPOSxx-OSLBORD
Select BO signal (BO*-RB) from signal list
*user-
preferred
BO read-back number
DPOSxx-FSLBORD
Select BO signal (BO*-RB) from signal list
*user-
preferred
BO read-back number
DPOSxx-OEXBORD
Select BO signal (BO*-RB) from signal list
*user-
preferred
BO read-back number
DPOSxx-FEXBORD
Select BO signal (BO*-RB) from signal list
*user-
preferred
BO read-back number
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......