6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1020 -
8.2.5
Setting
EVENTRECORD(Function ID: 200710)
Setting items
Range
Unit
Contents
Default
Note
End of E.Record-1
0 to 768
– The last position of the event group1 (Level1)
256
End of E.Record-2
0 to 768
– The last position of the event group2 (Level2)
512
Trigger ID1
(Preferred DataID)
– Trigger signal1 for the operation
See tables in this
section
Tigger Mode1
On / Off / On-Off /
Change
– Mode setting for the detection
Event name1
(Preferred name)
– Name of the trigger signal1
Trigger ID2
(Preferred DataID)
– Trigger signal2 for the operation
Tigger Mode2
On / Off / On-Off /
Change
– Mode setting for the detection
Event name2
(Preferred name)
– Name of the trigger signal2
……
……
– ……
……
……
– ……
……
……
– ……
Trigger ID768
(Preferred DataID)
– Trigger signal768 for the operation
Tigger Mode768
On / Off / On-Off /
Change
– Mode setting for the detection
Event name768
(Preferred name)
– Name of the trigger signal768
8.2.6
Signal (Data ID)
Signal monitoring point
EVENTRECORD (Function ID: 200710)
Name
Element ID
Description
ER1_CLR
3001001001
Clearing the data in Event group1
ER2_CLR
3002001001
Clearing the data in Event group2
ER3_CLR
3003001001
Clearing the data in Event group3
POWER ON
3100001001
Detection of switch On
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......