Safety instructions
WARNING!
Obey these instructions. If you ignore them, injury or death, or damage
to the equipment can occur. If you are not a qualified electrical professional, do
not do electrical installation or maintenance work.
•
Do not do work on the drive, motor cable, motor, or control cables when the drive is
connected to the input power. Before you start the work, isolate the drive from all
dangerous voltage sources and make sure that it is safe to start the work. Always wait for
5 minutes after disconnecting the input power to let the intermediate circuit capacitors
discharge.
•
Do not do work on the drive when a rotating permanent magnet motor is connected to it.
A rotating permanent magnet motor energizes the drive, including its input and output
terminals.
Unpack the delivery
Keep the drive in its package until you are ready to install it. After unpacking, protect the drive
from dust, debris and moisture.
Make sure that these items are included:
•
Drive
•
Quick installation and start-up guide
•
A set of spare EMC screws
Make sure that there are no signs of damage to the items.
Reform the capacitors
If the drive has not been powered up for a year or more, you must reform the DC link
capacitors. The manufacturing date is on the type designation label. Refer to
Capacitor
reforming instructions (3BFE64059629 [English]).
Select the cables and fuse
•
Select the power cables. Obey the local regulations.
Input power cable:
ABB recommends to use symmetrical shielded cable (VFD cable) for
the best EMC performance.
Motor cable:
Use symmetrical shielded cable (VFD cable) for the best EMC performance.
Symmetrical shielded cable also reduces bearing currents, wear, and stress on motor
insulation.
Power cable types:
In IEC installations, use copper or aluminum cables (if permitted). In
UL installations, use only copper cables.
Current rating:
max. load current.
Voltage rating:
min. 600 V AC.
Temperature rating:
In IEC installations, select a cable rated for at least 70
°C (158
°F)
maximum permissible temperature of conductor in continuous use. In UL installations,
select a cable rated for at least 75
°C (167
°F).
Size:
Refer to ACS280 Hardware Manual (
3AXD50001017705 [English]).
•
Select the control cables. Use double-shielded twisted-pair cable for analog signals. Use
double-shielded or single-shielded cable for the digital, relay and I/O signals. Do not run
24 V and 115/230 V signals in the same cable.
•
Protect the drive and input power cable with the correct fuses. Refer to
.
Examine the installation area
The drive has a degree of protection of IP00 / UL open type as standard and must be installed
into cabinet/enclosure.
Examine the site where you will install the drive. Make sure that:
•
There is sufficient free space around the drive for cooling, maintenance, and operation.
For the minimum free space requirements, refer to
.
•
The ambient conditions meet the requirements. Refer to
.
•
The installation surface is strong enough to support the weight of the drive. Refer to
•
The installation surface, floor and materials near the drive are not flammable.
•
There are no sources of strong magnetic fields such as high-current single-core
conductors or contactor coils near the drive. A strong magnetic field can cause
interference or inaccuracy in the operation of the drive.
•
The installation direction should obey the instruction in hardware manual.
(
3AXD50001017705 [English]).
Install the drive
WARNING! ACS280 drive may become damaged if operated without a suitable
heat-sink. Do not operate the drive without providing suitable heat-sink capacity
for the drive and application requirement.
•
ACS280 must be mounted onto a suitable flat metallic surface with sufficiently low
thermal resistance to allow dissipation of the heat produced.
For detailed information,
please refer to the
Planning the cooling of the drive in ACS280 Hardware Manual
(
3AXD50001017705 [English]).
1. Make marks onto the surface for the mounting holes. Refer to
.
Download the mounting template on
library.abb.com
.
2. Drill the holes for the mounting screws. If necessary, install suitable plugs or anchors into
the holes.
3. Apply the thermal compound onto the cold-plate surface of the drive. About how to
properly apply the thermal compound, refer to
ACS280 Hardware Manual
(
3AXD50001017705 [English]).
4. Put the drive onto the mounting holes.
5. Tighten the mounting screws.
Measure the insulation resistance
Drive:
Do not do voltage tolerance or insulation resistance tests on the drive, because this can
cause damage to the drive.
Input power cable:
Before you connect the input power cable, measure the insulation of the
input power cable. Obey the local regulations.
Motor and motor cable:
1.
Make sure that the motor cable is connected to the motor and disconnected from the
drive output terminals T1/U, T2/V and T3/W.
2.
Use a voltage of 1000
V DC to measure the
insulation resistance between each phase
conductor and the protective earth
conductor. The insulation resistance of an
ABB motor must be more than 100 Mohm (at
25 °C [77 °F]). For the insulation resistance of
other motors, refer to the manufacturer’s
documentation.
Moisture in the motor decreases the
insulation resistance. If you think that there
is moisture in the motor, dry the motor and
do the measurement again.
Make sure that the drive is compatible with the
grounding system
You can connect all drive types to a symmetrically grounded TN-S system (center-grounded
wye). The drive is delivered with the metal EMC and VAR screws installed. There are also spare
plastic EMC/VAR screw included in drive delivery. The table shows when to use the metal
EMC/VAR screw
(connect the internal EMC filter) or plastic EMC/VAR screw(disconnect the
internal EMC filter).
Note:
Not all ACS280 drives have the EMC/VAR screw, check hardware manuals for details.
Connect the power cables
Connection diagram
(shielded cables)
1.
Disconnecting device.
2.
Two protective earth (ground) conductors. Drive safety standard IEC/EN61800-5-1
requires two PE conductors, if the cross-sectional area of the PE conductor is less than
10 mm
2
Cu or 16 mm
2
Al. For example, you can use the cable shield in addition to the
fourth conductor.
3.
Use a separate grounding cable or a cable with a separate PE conductor for the line side,
if the conductivity of the fourth conductor or shield does not meet the requirements for
the PE conductor.
4.
Use a separate grounding cable for the motor side, if the conductivity of the shield is not
sufficient, or if there is no symmetrically constructed PE conductor in the cable.
5.
Do the 360-degree grounding of the cable shield for the motor cable and brake resistor
cable outside the drive and as close to the power terminals as possible. It is also
recommended for the input power cable.
6.
Brake resistor and resistor cable (optional).
Connection procedure
(shielded cables)
For the tightening torques, refer to ACS280 Hardware Manual (
3AXD50001017705 [English]).
1.
Strip the motor cable.
2. Twist the motor cable shield into a
bundle, mark it and connect it to
the grounding screw and ground
the shield under the grounding
clamp outside the drive close to
the terminals.
3. Connect the phase conductors of
the motor cable to terminals T1/U,
T2/V and T3/W.
4. If you use a brake resistor, connect
the brake resistor cable to
terminals R- and UDC+. Use a
shielded cable and ground the
shield under the grounding clamp
outside the drive close to the
terminals.
5. Strip the input power cable.
6. If the input power cable has a shield, ground the shield under the grounding clamp
outside the drive close to the terminals. Then twist the shield into a bundle, mark it and
connect it to the grounding terminal.
7. Connect the PE conductor of the input power cable to the grounding terminal. If
necessary, use a second PE conductor, connect to a second PE connection point which
must be well conducted with the drive's cold plate and as close to the drive as possible.
8. In 3-phase drives, connect the phase conductors of the input power cable to terminals L1,
L2 and L3. In 1-phase drives, connect the phase and neutral conductors to terminals L and
N.
9.
Mechanically attach the cables on the outside of the drive.
Connect the control cables
Connection procedure
Do the connections according to your
control requirements. Keep the signal
wire pairs twisted as near to the
terminals as possible to prevent
inductive coupling.
1. Strip a part of the outer shield of
the control cable for grounding.
2. Use a screw to connect the outer
shield to the grounding tab.
3. Strip the control cable conductors.
4. Connect the conductors to the
correct control terminals. Insert
the conductor into a push-in
terminal. To release, pull the
conductor with pushing the open/
close button all the way down
firmly with a flathead screwdriver.
5. Mechanically attach the control
cables on the outside of the drive.
Default I/O connections (ABB standard macro)
For detailed information, please refer to
ABB Standard Marco in ACS280 Firmware Manual
(
3AXD50001017729 [English]).
Ratings
Fuses and typical power cable sizes
For detailed information, please refer to the
Technical Data in ACS280 Hardware Manual
(
3AXD50001017705 [English]).
Terminal data for the power cables
For detailed information, please refer to the
Technical Data in ACS280 Hardware Manual
(
3AXD50001017705 [English]).
Free space requirements
For detailed information, please refer to the
Mechanical installation in ACS280 Hardware
Manual (
3AXD50001017705 [English]).
Dimensions and weights
Ambient conditions
Markings
The applicable markings are shown on the type label of the product.
Safe torque off (STO)
The drive has a Safe torque off function (STO) in accordance with IEC/EN 61800-5-2. It can be
used, for example, as the final actuator device of safety circuits that stop the drive in case of
danger (such as an emergency stop circuit).
When activated, the STO function disables the control voltage of the power semiconductors
of the drive output stage, thus preventing the drive from generating the torque required to
rotate the motor. The control program generates an indication as defined by parameter
31.22.
If the motor is running when Safe torque off is activated, it coasts to a stop. Closing the
activation switch deactivates the STO. Any faults generated must be reset before restarting.
The STO function has a redundant architecture, that is, both channels must be used in the
safety function implementation. The safety data given is calculated for redundant use, and
does not apply if both channels are not used.
WARNING!
The STO function does not disconnect the voltage from the main and
auxiliary circuits of the drive.
Notes:
•
If stopping by coasting is not acceptable, stop the drive and machinery using the
appropriate stop mode before activating the STO.
•
The STO function overrides all other functions of the drive.
Wiring
The safety contacts must open/close within 200 ms of each other.
Double-shielded twisted-pair cable is recommended for the connection. The maximum length
of the cabling between the switch and the drive control unit is 300 m (1000 ft). Ground the
shield of the cable at the control unit only.
Validation
To ensure the safe operation of a safety function, a validation test is required. The test must
be carried out by a competent person with adequate expertise and knowledge of the safety
function. The test procedures and report must be documented and signed by this person.
Validation instructions of the STO function can be found in the drive hardware manual.
Technical data
•
Minimum voltage at S1 and S2 to be interpreted as “1”: 13 V DC
•
STO reaction time (shortest detectable break): 1 ms
•
STO response time: 5 ms (typical), 10 ms (maximum)
•
Fault detection time: Channels in different states for longer than 200 ms
•
Fault reaction time: Fault detection time + 10 ms
•
STO fault indication (parameter
31.22) delay: < 500 ms
•
STO warning indication (parameter
31.22) delay: < 1000 ms
•
Safety integrity level (EN 62061): SIL 3
•
Performance level (EN ISO 13849-1): PL e
The drive STO is a type A safety component as defined in IEC 61508-2.
For the full safety data, exact failure rates and failure modes of the STO function, refer to the
drive hardware manual.
For detailed information about STO, please refer to
Safe Torque Off chapter in ACS280
Hardware Manual (
3AXD50001017705 [English]).
Declaration of conformity
—
ABB MACHINERY DRIVES
ACS280 Cold-Plate drives
Quick installation and start-up guide
Ecodesign information
(EU 2019/1781)
About this document
3AXD50001017743 Rev A
Bilingual
2023-07-10
© 2023 ABB All rights reserved.
Original instructions.
R1, R2
M1
M2
M3
6
12
3-
φ
6
U1
V1
W1
PE
M
3~
ohm
U1-PE, V1-PE, W1-PE
Screw
label
Grounding systems
Symmetrically grounded
TN-S systems (center-
grounded wye)
Corner-grounded delta,
midpoint-grounded
delta and TT systems
IT systems (ungrounded or
high-resistance grounded)
EMC
Metal
Plastic
Plastic
VAR
Metal
Metal
Plastic
Terminals
Descriptions
Digital I/O connections
3
24 V
Aux. +24 V DC, max 200 mA
4
DGND
Aux. voltage output common
1
DI1
Stop (0) / Start (1)
2
DI2
Forward (0) / Reverse (1)
Analog I/O
5
AI1
Speed reference (0…10V)
6
AI2
Not used
9
GND
Analog output circuit common
8
AO1/DO1
AO: Output frequency (0…10V)
7
10V
Ref. v10 V DC
CANopen protocal
10
CAN-H
Embedded CANopen (CAN)
11
CAN-L
12
GND
EIA-485 Modbus RTU
13
A-
Embedded Modbus RTU (EIA-485)
14
B+
15
GND
Relay output
16
RO NC
No fault [Fault (-1)]
17
RO COM
18
RO NO
Safe torque off (STO)
19
S+
Safe torque off function (STO).
Connected at factory.
Drive starts only when both circuits
are closed."
20 SGND
21
S1
22
S2
ACS280-
04...
Input current
Output ratings
No
choke
With
choke
Max.
current Nominal use
Light-duty use
Heavy-duty use
I
1
I
1
I
max
I
2
P
N
I
Ld
P
Ld
I
Hd
P
Hd
A
A
A
A
kW
A
kW
hp
A
kW
hp
1-phase
U
N
= 230 V (range 200
…
240 V)
03A7-1
6.9
4.8 4.3
3.7
0.55
3.5
0.55
0.75
2.4
0.37
0.5
06A9-1
12.6 9.2
8.1
6.9
1.1
6.6
1.1
1.5
4.5
0.75
1
09A8-1
21.8 17
13.5
9.8
2.2
9.3
2.2
2
7.5
1.5
2
12A2-1
23.9
21.1
17.6
12.2
3
11.6
3
3
9.8
2.2
3
3-phase
U
N
= 230 V (range 200
…
240 V)
03A7-2
4.5
3.7
4.3
3.7
0.55
3.5
0.55
0.75
2.4
0.37
0.5
06A9-2
7.1
6.9
8.1
6.9
1.1
6.6
1.1
1.5
4.5
0.75
1
09A8-2
12.1
9.8
13.3
9.8
2.2
9.3
2.2
3
7.4
1.5
2
12A2-2
16.2
1
2.2
17.6
12.2
3
11.6
3
3
9.8
2.2
3
17A5-2
21.2
17.5
22
17.5
4
16.7
4
5
12.2
3
3
PE
PE
L1
L2
L3
R-
R+
UDC+ UDC-
U1
W1
M
PE
3
T1/
U
T2/
V
T3/
W
V1
L1
L2
L3
(L)
(N)
2
3
4
5
ACS280
1
6
3-phase
U
N
= 400 V (range 380
…
415 V)
03A3-4
4.6 2.5 4.3
3.3
1.1
3.0
1.1
-
2.4
0.75
-
05A6-4
9
4.6 7.2
5.6
2.2
4.8
2.2
-
4
1.5
-
07A2-4
12 6
10.1
7.2
3
6
3
-
5.6
2.2
-
09A4-4
13 8
13
9.4
4
7.6
4
-
7.2
3
-
12A6-4
17.4
12.6
16.9
12.6
5.5
11
5.5
-
9.4
4
-
3-phase
U
N
= 460 V (range 440
…
480 V)
03A3-4
3.5
2.1
4.3
-
-
3.0
-
1.5
2.1
-
1
05A6-4
6.9
3.8
7.2
-
-
4.7
-
3
3.4
-
2
07A2-4
9.2
5
10.1
-
-
6.0
-
3
4.8
-
3
09A4-4
10.3
6.7
13
-
-
7.6
-
5
6.3
-
3
12A6-4
14.8
11
16.9
-
-
11
-
7.5
7.6
-
5
Frame size
Front
Top
Other sides
mm
in
mm
in
mm
in
R1
20
0.8
20
0.8
0
0
R2
30
1.2
30
1.2
0
0
ACS
280
Dimensions
Weights
H
W
D
M1
M2
M3
mm in
mm
in
mm
in
mm
in
mm
in
mm
in
kg
lb
R1
145 5.71 135 5.31
90 3.54 129 5.06 133 5.24 76
2.97 0.95
2.1
R2
196 7.72 141 5.55
90 3.54 134 5.26 182 7.17 90 3.54
1.33
2.94
Requirement
During operation (installed for stationary use)
Installation site altitude
0 … 1000 m above sea level without derating.
1000 … 2000 m above sea level with derating.
Surrounding air
temperature
-10... +50 °C (14 … 122 °F) without derating.
No frost allowed.
Relative humidity
<95% (IEC 60068-2-78) without condensation
Contamination levels
No conductive dust permitted.
Shock or free fall
Not permitted
CE
UR
UKCA
EIP green
WEEE
TÜV Nord
ACS280-
04...
Input current
Output ratings
No
choke
With
choke
Max.
current Nominal use
Light-duty use
Heavy-duty use
I
1
I
1
I
max
I
2
P
N
I
Ld
P
Ld
I
Hd
P
Hd
A
A
A
A
kW
A
kW
hp
A
kW
hp
H
W
D