6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 272 -
Table 2.16-2 Values k, a, c for pre-programmable IDMT and user-programmable IDMT
Set item
k
a
C
IDMT
1
1
0
User-programmable
(Original)
0.00000 – 500.00000
by 0.00001 step
0.00000 – 10.00000
by 0.00001 step
0.00000 – 10.00000
by 0.00001 step
Drop-off characteristic
The user should set the time for resetting in the IDMT characteristic. Figure 2.16-3 shows
examples of the pick-up and the drop-off relevant to both the fault occurrences and the
operation time. The UVS1 element has a time counter that increases in response to the fault
occurrence and duration. This figure also shows the increment degree of the time counter for
the fault occurrences.
As for an intermittent fault (the former in the figure), the time counter does not reach
the trip level. In the other word, the UVS1 element will be paralyzed in the reset time
[
TUVS1R
]. If a series of fault occurs, the time counter increase corresponding to the duration
of series faults. When the time counter reaches the trip level, then the UVS1 element issues a
trip signal after a certain delay. After issuing the trip signal, if a series of fault disappears
completely, the operation of the UVS1 element is expired after the reset time [
TUVS1R
].
When the user requires resetting the operation of the UVS1 element immediately, setting
zero for the settings [
TUVS1R
] is needed. Consequently, when a voltage is recovered over the
reset threshold (drop-off), the operation of the UVS1 element is reset promptly.
Figure 2.16-3 Faults occurrences and reset operation when DT being applied
Condition fault occurrence
Fault observation by the relay
Issue of trip command
Trip level
Incrimination of time counter
corresponding to the fault
duration.
T
1
T
1
: Resetting time set by the user
T
2
: Actual resetting time in the relay operation
T
3
: Time gap between fault occurrence and relay start time
Tripping
T
1
T
1
T
1
T
2
T
2
T
3
Intermittent fault
A series fault
Relay operation reset
Reset of time counter
Increment process in time
counter
Value maintenance of time counter
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......