6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 471 -
GCNT01 function (Function ID:
54001)
“GCNT01_SLD_CSCN”
(540001 8A0E011E76)
GCNT01_CMM_REQ
Command
“Remote-Reset-Control”
Either
“SBO mode” or “DIR mode”
(e.g.,
“ctlmodel” in IEC61850
*
)
In SBO operate
In DIR operate
Select
“Failed”
540001 700E016D09
To BO connection
Input
Output
Select logic in GCNT01
0.2s
0
t
0.3s
0
t
&
&
&
Complete
“Automatic sequence control function (AQEQ)
§
” in progress
ASEQ_MULTI_SEL
Select condition
‡
1
≥
Select command
Operate command
For SBO operation
For DIR operation
To
“Wait for a command”
To
“Wait for a next
command
”
“GCNT01_SLF_CSCN”
(540001 8B0E011E7B)
Figure 3.7-6 Select ‘Reset’ in GCNT01
††
‡Note: A “select condition” signal is provided from the select condition logic. For more
information, see Figure 3.7-7.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The GCNT01 operation is blocked for the ASEQ function when
it is in operation. For more information on the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
*Note: The GNCT01 function can run in either the “SBO mode” or the “DIR mode” using
a signal called “ctlmodel” when communication is implemented using IEC61850.
To use this signal, the user should map it for IEC61850 communication.
††
Note: To identify the input and output points of the other GCNT02–GCNT32 logics, see
Table 3.7-2 for the inputs and Table 3.7-5 for the outputs.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......