6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 538 -
“SPOS01_SL_BO_FLG”
(510001
_
8501011F76)
BIO module
BO2
“SPOS01_OEX_BO”
(510001
_
8201011DD3)
“BO2-RB”
(200B01
_
8102011113)
BO3
“SPOS01_FEX_BO”
(510001
_
8101011DD0)
“BO3-RB”
(200B01
_
8202021113)
SW2 is driven with
BO2 at IO#1
SW3 is driven with
BO3 at IO#1
Plus (+)
SW 3
SW 2
Minus (
−)
43SW
On
Command
Off
Command
SW1 is not driven with
any BO1
SW 1
Plus (+)
Physical BO is
virtualized.
Remote/Local end
Select
command
ON/OFF
Operate-On
command
Operate-Off
command
Figure 4.1-39 Contact health check setting and 43SW diagram for example #3
Table 4.1-25 PLC monitoring points (Output signal for event suppression function in SPOSxx)
Signal Number
Signal Name
Description
510001 0001011001
SPOS01_STATE
Status of SPOS01
510001 0001021001
SPOS02_STATE
Status of SPOS02
510001 0001031001
SPOS03_STATE
Status of SPOS03
….
….
….
510001 0001141001
SPOS20_STATE
Status of SPOS20
510001 8101011F59
SPOS01_F_QLT_SPP
Event suppression detected (SPOS01)
510001 8101021F59
SPOS02_F_QLT_SPP
Event suppression detected (SPOS02)
510001 8101031F59
SPOS03_F_QLT_SPP
Event suppression detected (SPOS03)
….
….
….
510001 8101141F59
SPOS20_F_QLT_SPP
Event suppression detected (SPOS20)
Table 4.1-26 PLC monitoring points (Output of select signal in SPOSxx)
Signal Number
Signal Name
Description
510001 8501011F76
SPOS01_SL_BO_FLG
Select command signal in SPOS01
510001 8501021F76
SPOS02_SL_BO_FLG
Select command signal in SPOS02
510001 8501031F76
SPOS03_SL_BO_FLG
Select command signal in SPOS03
….
….
….
510001 8501141F76
SPOS20_SL_BO_FLG
Select command signal in SPOS20
Table 4.1-27 PLC monitoring points (Output of operate signal in SPOSxx)
Signal Number
Signal Name
Description
510001 8201011DD3
SPOS01_OEX_BO
SPOS01 operate (ON) command for Binary Output.
510001 8201021DD3
SPOS02_OEX_BO
SPOS02 operate (ON) command for Binary Output.
510001 8201031DD3
SPOS03_OEX_BO
SPOS03 operate (ON) command for Binary Output.
…
…
…
510001 8201141DD3
SPOS20_OEX_BO
SPOS20 operate (ON) command for Binary Output.
510001 8101011DD0
SPOS01_FEX_BO
SPOS01 operate (OFF) command for Binary Output.
510001 8101021DD0
SPOS02_FEX_BO
SPOS02 operate (OFF) command for Binary Output.
510001 8101031DD0
SPOS03_FEX_BO
SPOS03 operate (OFF) command for Binary Output.
…
….
….
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......