11.3Front panel
11-7
11.3 Front panel
11.3.1 Front panel configuration
LED display
Name of signal
State
Content
RDY status lamp
(green)
ON
Main power supply established and power supply module alarm has not occurred.
Main power establishment conditions:
Three-phase 400V was applied to the main power supply of the power supply module, and the
rectified main power supply DC voltage exceeded the main power supply establishment
voltage, and the main power supply establishment wait time had elapsed.
OFF
Main power shut-off or power supply module alarm occurrence status.
Main power shutdown conditions:
- Initializing.
- After the main power supply is established, the main power supply is shut off, and the main
power supply DC voltage is less than the main power supply establishment voltage.
ERR status lamp
(red)
ON
Power supply module alarm detection.
Blinking
No power supply module alarm/warning detection.
OFF
No power supply module alarm/warning, or initializing.
Summary of Contents for MINAS A6 Series
Page 10: ...Table of contents x Blank page...
Page 11: ...1 Introduction...
Page 26: ...Introduction 1 16 Blank page...
Page 27: ...2 Interface Specifications...
Page 46: ...Interface Specifications 2 20 Blank page...
Page 47: ...3 Front Panel Specifications...
Page 57: ...4 Basic Functions...
Page 85: ...5 Auto Tuning Functions...
Page 151: ...6 Application Functions...
Page 185: ...7 Protective Functions...
Page 224: ...Protective Functions 7 40 Blank page...
Page 225: ...8 Advanced Safety Functions...
Page 230: ...Advanced Safety Functions 8 6 When test pulse is used Duplex safety input Safety input...
Page 245: ...9 List of Parameters...
Page 281: ...10 Timing Chart...
Page 290: ...Timing Chart 10 10 Blank page...
Page 291: ...11 Power Supply Module...